Satellite SCADA for treatment plants | ISA

http://www.isa.org/PrinterTemplate.cfm?Section=InTech_Home1&tem...

09 April 2001

by Eric Silverman

The technology is available, but is it cost effective?
Dedicated, satellite-based business communications using relatively small dish antennas, or very small aperture terminals (VSATs), are no longer only for governments and colossal corporations. An industry study predicted in 1990 that supervisory control and data acquisition (SCADA) services would become a market for VSAT technology by the mid-1990s. VSAT SCADA is now an important tool in the oil, pipeline, and electric utility markets, fulfilling the prediction. VSAT has been successful in these industries, according to Satellite Communications contributor Phil Samuels, because the "electric, gas, and liquid transmission systems transit vast distances, often far from telecommunications and electrical power sources. Monitoring of these transmission facilities and the ability to take action to control their operations are important for inventory, regulatory, and safety reasons." Following its successful entry into these markets, the VSAT industry is now looking for new SCADA applications. One market to attract its interest is water and wastewater treatment, currently about 0.5% of VSAT SCADA installations. A close look suggests VSAT might soon play an important role in water and wastewater plant SCADA.

The VSAT SCADA system for a typical water or wastewater treatment plant with remote sites would have the following components: Eleven remote terminal units (RTUs), weatherized enclosures that contain the programmable logic controllers (PLCs) that collect data from the local field instruments. The receiver/transmitter boards and LAN interface cards for data transmission and protocol conversions between the PLC and VSAT are also inside the RTU. The VSAT, a 1.8-meter dish antenna mounted on a pole or building that communicates with the geostationary earth orbiter (GEO). VSAT transmissions to the GEO are usually in the 12-14 gigahertz range in the U.S. and 4-6 gigahertz range outside the U.S. A human-machine interface (HMI) computer, used by the plant operator to monitor and control processes at the RTU sites. A master PLC, located at the control room, that polls the remote VSAT units at the RTUs. The polling sequence sends the appropriate commands for transmitting and receiving data from the RTUs. The indoor unit processes communications commands and forwards them for transmission through the VSAT unit.

The cost of the system described above was compared with the cost of dedicated telephone lines and spread-spectrum radios (SSRs), the most common communication technologies now used.

1 of 3

3/28/2012 2:03 PM

Satellite SCADA for treatment plants | ISA

http://www.isa.org/PrinterTemplate.cfm?Section=InTech_Home1&tem...

The end result was that the installation and hardware costs for VSATs far exceeded those of telephone and SSR systems. Capital costs are only part of the picture, however; operational costs play a role, too. The benefits of VSAT begin to appear once operational factors are considered. Compared with leased telephone lines, for instance, monthly VSAT service charges are competitive when data rates are low. This is realistic for the water and wastewater industry because most remote sites have very small data requirements. Mean time between failure and uptime are similar for the three technologies. However, system monitoring is the strongest operational feature of VSAT technology. Hughes Network Systems and Nova-Net offer 24-hour, 7-days-a-week network monitoring from their Network Management Center. Don Rowe with Nova-Net said, "Very often, the customer is more concerned about the services that are provided, like monitoring of his network, the responsiveness of the network operators, how well they will work with the customer, etc. For example, it is our goal to call a customer about a detected event that might be a problem before his own system tells him that something might be amiss." This kind of customer service simply isn't available from SSR vendors and telephone companies. The transmission speeds for these technologies are by no means "cutting edge." Data transfer rates are not critical in the water/ wastewater industry, however, because the monitored processes are rarely time sensitive. Therefore, the speeds shown for all three technologies are adequate. The propagation delays are significantly higher for VSAT than for the other technologies because a transmission is required to travel more than 20,000 miles before reaching its destination. Like transmission speed, propagation delays of these magnitudes are insignificant in this particular industry. The water level in a tank or well, for example, doesn't change so rapidly that a pump delay of a few seconds is decisive. Transmission range is where VSATs shine. If the remote sites are on the order of 20 30 miles away, then VSAT becomes an important communications technology. The fact that VSAT is not distance dependent and does not have transmission constraints allows this technology to go where SSRs and telephone lines cannot.

VSAT technology offers benefits to SCADA installations for only a limited number of cases—those where the operational benefits and savings can outweigh the capital costs. Two conditions that affect this are plant geography and the central monitoring service of the VSAT service provider. SSR and telephone, for example, may not be options if the remote location is more than about 20 miles away or is unavailable to line-of-sight transmissions, such as when the RTUs are in a very desolate area not served by telephone or the terrain is very mountainous. VSATs are not susceptible to these difficulties and can even be specified to use solar power. The proactive approach of most VSAT providers means they become a sort of extension of the plant's staff. This can mean operational savings, with less staff time devoted to system maintenance. The more VSAT SCADA sites a plant has, the greater the corresponding savings. IT

2 of 3

3/28/2012 2:03 PM

Satellite SCADA for treatment plants | ISA

http://www.isa.org/PrinterTemplate.cfm?Section=InTech_Home1&tem...

Comparing costs Transmission characteristics VSAT benefits

Eric Silverman is an engineer with Camp Dresser & McKee, Inc. in Cambridge, Mass.

3 of 3

3/28/2012 2:03 PM

Similar Documents

Free Essay

Nit-Silchar B.Tech Syllabus

...NATIONAL INSTITUTE OF TECHNOLOGY SILCHAR Bachelor of Technology Programmes amï´>r¶ JH$s g§ñWmZ, m¡Úmo{ à VO o pñ Vw dZ m dY r V ‘ ñ Syllabi and Regulations for Undergraduate PROGRAMME OF STUDY (wef 2012 entry batch) Ma {gb Course Structure for B.Tech (4years, 8 Semester Course) Civil Engineering ( to be applicable from 2012 entry batch onwards) Course No CH-1101 /PH-1101 EE-1101 MA-1101 CE-1101 HS-1101 CH-1111 /PH-1111 ME-1111 Course Name Semester-1 Chemistry/Physics Basic Electrical Engineering Mathematics-I Engineering Graphics Communication Skills Chemistry/Physics Laboratory Workshop Physical Training-I NCC/NSO/NSS L 3 3 3 1 3 0 0 0 0 13 T 1 0 1 0 0 0 0 0 0 2 1 1 1 1 0 0 0 0 4 1 1 0 0 0 0 0 0 2 0 0 0 0 P 0 0 0 3 0 2 3 2 2 8 0 0 0 0 0 2 2 2 2 0 0 0 0 0 2 2 2 6 0 0 8 2 C 8 6 8 5 6 2 3 0 0 38 8 8 8 8 6 2 0 0 40 8 8 6 6 6 2 2 2 40 6 6 8 2 Course No EC-1101 CS-1101 MA-1102 ME-1101 PH-1101/ CH-1101 CS-1111 EE-1111 PH-1111/ CH-1111 Course Name Semester-2 Basic Electronics Introduction to Computing Mathematics-II Engineering Mechanics Physics/Chemistry Computing Laboratory Electrical Science Laboratory Physics/Chemistry Laboratory Physical Training –II NCC/NSO/NSS Semester-4 Structural Analysis-I Hydraulics Environmental Engg-I Structural Design-I Managerial Economics Engg. Geology Laboratory Hydraulics Laboratory Physical Training-IV NCC/NSO/NSS Semester-6 Structural Design-II Structural Analysis-III Foundation Engineering Transportation Engineering-II Hydrology &Flood...

Words: 126345 - Pages: 506

Premium Essay

Test Paper

...CompTIA Security+: Get Certified Get Ahead SY0-401 Study Guide Darril Gibson Dedication To my wife, who even after 22 years of marriage continues to remind me how wonderful life can be if you’re in a loving relationship. Thanks for sharing your life with me. Acknowledgments Books of this size and depth can’t be done by a single person, and I’m grateful for the many people who helped me put this book together. First, thanks to my wife. She has provided me immeasurable support throughout this project. The technical editor, Steve Johnson, provided some good feedback throughout the project. If you have the paperback copy of the book in your hand, you’re enjoying some excellent composite editing work done by Susan Veach. I’m extremely grateful for all the effort Karen Annett put into this project. She’s an awesome copy editor and proofer and the book is tremendously better due to all the work she’s put into it. While I certainly appreciate all the feedback everyone gave me, I want to stress that any technical errors that may have snuck into this book are entirely my fault and no reflection on anyone who helped. I always strive to identify and remove every error, but they still seem to sneak in. About the Author Darril Gibson is the CEO of YCDA, LLC (short for You Can Do Anything). He has contributed to more than 35 books as the sole author, a coauthor, or a technical editor. Darril regularly writes, consults, and teaches on a wide variety of technical...

Words: 125224 - Pages: 501

Free Essay

Maglev

...*3963103* [3963] – 103 T.E. (Petroleum) (Semester – I) Examination, 2011 DRILLING & PRODUCTION OPERATIONS (2003 Course) Time : 3 Hours Max. Marks : 100 Instructions : 1) Question Nos. 1 and 5 are compulsory. Out of the remaining attempt 2 questions from Section I and 2 questions from Section II. 2) Answers to the two Sections should be written in separate books. 3) Neat diagrams must be drawn wherever necessary. 4) Black figures to the right indicate full marks. 5) Use of Logarithmic Tables, Slide Rule, Mollier Charts, Electronic Pocket Calculator and Steam Tables is allowed. 6) Assume suitable data, if necessary. SECTION – I 1. What are different systems on a drilling rig ? Explain any one in detail with suitable diagramme. 18 2. a) Calculate Bottom hole pressure if well depth is 2500 m and mud weight is 1.2 gm/cc. b) Calculate mud weight if mud gradient is 0.87 psi/ft. ′ c) Calculate volume bbl/meter for drill pipe O.D. = 5′ inch and I.D. = 4.276 inch. 2 2 2 10 8 8 16 d) Draw circulation system on a drilling rig. 3. a) Discuss IADC classification of a bit in details. b) Discuss different factors affecting rate of penetration in details. 4. Write short note on : i) Coring ii) Fishing tools iii) BOP iv) Directional well P.T.O. [3963] – 103 -2- *3963103* SECTION – II 5. a) Discuss different types of casings and function of the casings in brief. b) Discuss different types of well completion techniques. 6. a) Discuss primary cementation process with...

Words: 172166 - Pages: 689