PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing controllers. These instructions apply to the PXL-500, PXL-510 and Time and Attendance Terminals. For information regarding the use of the PXL-510 controller in connection with the NetworX1 NX-8E Alarm Panel, please refer to the NetworX NX-8E Alarm Panel Application Note (P/N 01919-001). For information regarding a Time and Attendance Terminal, please refer to the Time and Attendance Terminal Application Note (P/N 01943-001). NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation. NOTE: All references to the PXL-500 may be applied to the Time and Attendance Terminal.

Figure 1: The PXL-500/PXL-510 Controller

1. NetworX is a trademark of GE Interlogix.

Page 1 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

1.0

Specifications

Unit Dimensions • PXL-500/PXL-510 controller PCB - 6.75 inches high by 6.00 inches wide by 1.75 inches deep, including wiring connectors - (17.15 cm by 15.25 cm by 4.45 cm) • PXL-500/PXL-510 controller PCB with an LCD-1 Alpha/Numeric Display - 7.70 inches high by 6.00 inches wide by 1.75 inches deep, including wiring connectors - (19.60 cm by 15.25 cm by 4.45 cm) • PXL-500/PXL-510 controller PCB with an SB-593 Satellite Board (with or without an LCD-1 Alpha/Numeric Display) - 7.25 inches high by 6.00 inches wide by 1.75 inches deep, including wiring connectors - (18.45 cm by 15.25 cm by 4.45 cm) • Enclosure - 13 inches high by 9 inches wide by 4 inches deep - (33.02 cm by 22.86 cm by 10.16 cm) Operating Temperature/Humidity Range • 0°F to 140°F (-18°C to 60°C) • 0% to 90% Relative Humidity, non-condensing Controller Power Requirements • 12 VDC @ 1 A Current Draw • maximum current draw 270 mA for a controller plus reader current draw (refer to Table 1 for Reader current draw) • 120 mA max for a PXL-500/PXL-510 Controller • 150 mA max for an SB-593 Satellite Board Table 1: Reader Current Draw Reader Type MS-3000 Current Draw 50 mA MS-4000 50 mA MS-5000 100 mA MS-7000 200 mA

NOTE: If an electronic locking device (such as a magnetic lock, a door strike, or similar device) is to be driven by the same power supply as the PXL-500/PXL-510 controller, please ensure the power supply provides enough current to drive every device connected to that supply plus an adequate safety margin. AC power is not recommended. Controller Memory Retention • 5 year lithium battery back up to support controller RAM and real-time clock Output Relay Contact Rating • 1 Amp @ 24 VDC Input Device Configuration - 3 Inputs • Door Sense normally closed • Request to Exit normally open • Global Unlock normally open, or Auxiliary RTE A-Door normally open

Page 2 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

2.0

Cable Requirements

RS-232 Serial Cable • four conductor, shielded, stranded, AWG 24 wire (Belden 9534 or a larger gauge) • 50 feet maximum length (per RS-232 industry specification - greater lengths are not recommended) RS-485 Network Cable • two conductor, shielded, twisted pair, stranded, AWG 24 wire (Belden 9501 or a larger gauge) • 16,000 feet total network length • refer to the Network Wiring Application Note (P/N 01824-002) for specific network wiring information NOTE: When wiring the RS-485 terminal block connector, be sure to use the smallest connector provided. TB1 is smaller than the other terminal blocks and will only accept the smallest terminal block connector provided. Input Power • two conductor, stranded, AWG 18 wire (Belden 8461 or a larger gauge) • 200 foot maximum length for systems using an SB-293 with two readers NOTE: On long power cable runs, the cable resistance causes a drop in voltage at the end of the cable run. Be sure your power supply does provide 12 VDC at the end of the cable run. Earth Ground • Single conductor, AWG 18 wire (or a larger gauge)1 Keri Systems Proximity Readers • six conductor, shielded, stranded, AWG 24 wire (Belden 9536 or a larger gauge) • four conductor, shielded, stranded, AWG 24 wire (Belden 9534 or a larger gauge) for the MS-4000 only (there is no beeper or LED in the MS-4000) • see Table 2 for maximum cable lengths Table 2: Maximum Cable Lengths by Wire Gauge for Proximity Readers Cable Length by Wire Gauge Reader Type MS-3000 MS-4000 MS-5000 MS-7000 100 feet AWG 24 AWG 24 AWG 24 AWG 24 250 feet AWG 24 AWG 24 AWG 24 AWG 24 500 feet AWG 24 AWG 24 AWG 24 AWG 20

1. Ground wire is green with or without yellow tracer.

Page 3 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
Wiegand Compatible Readers • four to seven conductor, shielded, stranded, wire – depending upon the Wiegand reader’s requirements • a minimum gauge of AWG 24 is required for data transfer with a 500-foot maximum run length per Wiegand specification1 Input and Output Connections • two conductor, stranded, AWG 22 (or a larger gauge) NOTE: The Lock Output relay may require a heavier gauge of wire depending upon the current demands of the lock and the length of the lock wiring run. NOTE: If plenum cable is required, please reference the Belden plenum equivalent to the cables listed above.

3.0

When Installing Controllers

DO • plan ahead to meet power and any telephone requirements2 for your system (1 phone line for the modem connected to the host computer and one for each master PXL-500/PXL-510 in each network) • mount controllers in environmentally suitable areas - they require protection from weather and from temperature/ humidity extremes • if not using a KPS power supply, mount the controller at least 3 feet away from the controller's power supply to prevent EMI radiated from the power supply from affecting the controller • use the enclosure as a mounting template to mark drilling holes for permanent mounting • consider mounting requirements - central versus distributed - central mounting places all controllers in one location, running lengths of cables out to each door to support readers, inputs and outputs - distributed mounting places each controller near the door it supports running short lengths of cable out to each door, but running a long network communication cable • note the locations of the knockouts in the enclosures and remove the appropriate knockout for the easiest cable routing into the controller • route all controllers in a network in a single, continuous daisy-chain • route cables in accessible areas for ease of maintenance • connect all controllers to a quality earth ground3 • add transient suppression across electric devices attached to a controller output • use an isolation relay (P/N IRP-1, or equivalent) if attaching to an elevator, a parking gate, a turnstile, or any application using a large electric motor • verify the controller's supply voltage is 12 VDC – long power line runs cause a drop in voltage at the end of the run • verify proper operation of the host computer's COM port • for a single door application, install the reader to the TB-5, "A" reader connection • attach the reader to be used for card enrollment to the master controller (this reader can be used for access control as well as enrollment, but during the enrollment process the door associated with the enrollment reader will not allow access until the enrollment process is complete)

1. The wire gauge to use should be determined by the current draw requirements of the Wiegand device and the actual length of the cable run. A +5 VDC and a +12 VDC Wiegand device must have a full +5 VDC or +12 VDC at the device (long cable runs have a voltage drop across the length of the run due to the resistance in the cable). To ensure proper voltage is available at the device a larger gauge of wire (having less resistance) or a power supply at the Wiegand device may be required. 2. Phone lines are only needed for remote communication between host computer and network using a modem. 3. Ground wire is green with or without yellow tracer.

Page 4 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
DO NOT • make modem phone line connections through PBX telephone switching systems - most modems are not compatible with PBX systems leading to disconnection problems with the modem • locate the PXL-500/PXL-510 controller near EMI sources - EMI sources can affect the performance of the controller • use switching power supplies - they are EMI sources • route network and reader cables beside power cables - transients on the power cables may be picked-up by network and reader cables • stretch or over-tension cables • route over sharp objects • let the wires get tangled • mix PXL-500s/PXL-510s with PXL-100s in the same network • use a PXL-250 as the master on a network with PXL-500s/PXL-510s. The PXL-500/PXL-510 should always be the master controller. • route controllers in a network in a loop configuration • connect earth ground1 to the network cable shield - the PXL-500/PXL-510 automatically connects earth ground to the shield at one point on the network to prevent ground loops • use gender changer plugs when making RS-232 serial communication connections (unless you know it is a “straightthrough” plug) - gender changers may have internal wiring changes that can disrupt communications

Page 5 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

4.0
4.1

Wiring Instructions
Terminal Blocks

Refer to Figure 1 on page 1 for all wiring connections.

Figure 2: Connecting Wires and Removing Terminal Blocks NOTE: Screws on terminal blocks must be tightened securely.

4.2

Connecting the Earth Ground and the 12 VDC Power

Figure 3: Earth Ground and 12 VDC Power Connections

NOTE: TB2 is colored red to make it easier to tell it apart from the network connector.

4.3

Connecting a Keri Systems Proximity Reader to a PXL-500P/PXL-510P

Page 6 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
NOTE: Time and Attendace Terminals ordered with a reader installed come pre-wired. • • The "A" reader is wired to TB5. The "B" reader is wired to TB6.

Figure 4: Proximity Reader Connections

4.4

Connecting a Wiegand Compatible Reader to a PXL-500W/PXL-510W

The PXL-500W/PXL-510W controller can be configured to accept input from single-line LED, dual-line LED, and Essex keypad Wiegand input devices (through the Doors™ software). NOTE: The Wiegand Reader must transfer data according to the Security Industry Association's Wiegand Reader Interface Standard (document number AC-01D-96). Keri Systems, Inc. cannot guarantee the performance or reliability of Wiegand Readers that do not meet these data transfer guidelines. NOTE: All Keri Systems proximity readers use 12 VDC power while some Wiegand compatible readers use 5 VDC power. Check your reader's power requirements and verify jumper JP5 is set correctly per the Verify the Wiegand Reader Supply Voltage section on page 19. NOTE: The wire colors called out in Figures 5 and 6 are industry standard wire colors. However, some manufacturers may not follow these industry standard designations. Before installation, please refer to the Wiegand device’s manual to see if the device’s wire colors follow the industry standard. If not, then match the wire’s purpose to the call outs in Figures 5 and 6 before installation. NOTE: Time and Attendace Terminals ordered with a reader installed come pre-wired.

Make the following connections for a single-line LED or Essex Keypad Wiegand device. • The "A" input device is wired to TB5.

Page 7 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
• The "B" input device is wired to TB6.

Figure 5: Single-Line LED and Essex Keypad Wiegand Reader Connections Make the following connections for a dual-line LED Wiegand device. • The "A" input device is wired to TB5. • The "B" input device is wired to TB6.

Figure 6: Dual-Line LED Wiegand Reader Connections

4.5

Connecting a Door Status Input

Each PXL-500/PXL-510 is shipped with an installation kit including all necessary terminal blocks and transorbs. One of these terminal blocks has a jumper across pins 1 and 2. This terminal block is designated for use on TB-4. If a door switch is not used on the controller, this jumper prevents a continuous door open status alarm from being received by the controller. If a door switch is used, simply remove this jumper and install the door switch leads.

Page 8 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

Figure 7: Door Status Input Connections NOTE: A Door Switch must be installed on any door to which anti-passback is being applied for proper tracking of the anti-passback feature in the Doors program.

4.6

Connecting a Request to Exit (RTE) Input

Figure 8: Request to Exit Input Connections

4.7

Connecting a General Purpose Input

The general-purpose input is used in conjunction with the programmable input/output feature of the Doors access control software. There are three possible uses for the general-purpose input. • the master controller may be figured for either Global Unlock (see figure 9) or Auxiliary A-door RTE (see figure 10)

Page 9 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
• the slave unit may be figured for Auxiliary A-door RTE (see Figure 10)

Make the following connections for a Global Unlock input.

Figure 9: Global Unlock Input Connections

Make the following connections for an Auxiliary A-door RTE input.

Figure 10: Auxiliary A-Door RTE Input Connections

Page 10 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 4.8 Connecting an Alarm Output Relay

Figure 11: Alarm Output Relay Connections

4.9

Connecting a Fail-Safe Lock Output Relay

Figure 12: Fail-Safe Lock Output Relay Connections

4.10

Connecting a Fail-Secure Lock Output Relay

Figure 13: Fail-Secure Lock Output Relay Connections

Page 11 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 4.11 RS-485 Access Control Network Connection

Figure 14: RS-485 Network Connections

4.12

Communication Between the Access Control Network and Host Computer

Communication between the access control network and the host computer may be made via one of three ways.

Page 12 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
• • • A direct connect cable between master controller and host computer via the RS-232 serial port (see Section 4.12.1). Two modems making a remote connection between the master controller and host computer via the RS-232 serial port (see Section 4.12.2 on page 15 and Section 4.12.3 on page 16). Use of a LAN-50 or LAN-500 Universal Device Server to provide LAN/WAN Ethernet connectivity between Doors and one or more PXL networks. The LAN-50 makes use of the RS-232 serial port while the LAN-500 uses TB13 (see Figure 1 on page 1). For information on using a LAN-50 or LAN-500 Universal Device Server refer to the LAN-50/ LAN-500 Ethernet Communication Application Note (P/N 01881-003).

NOTE: When using a LAN-500 for ethernet communication, the jumpers across JP6 and JP7 must be removed for communication. For all other forms of communication, including use of a LAN-50, the jumpers must be placed across JP6 and JP7. NOTE: Do not use male/female gender changer plugs or 25-pin to 9-pin adapters when making RS-232 serial port connections. These devices may have internal wiring changes that can disrupt communications when implemented in conjunction with the Keri Systems serial wiring instructions. If you must use a gender changer plug, ensure it is a “straight-through” plug. NOTE: Keri Systems requires using modems from the same manufacturer at both the host computer and the access control network. This eliminates the possibility of incompatibilities between modems from two different manufacturers from affecting the communication between access control network and host computer. Keri Systems cannot be held responsible for problems caused by incompatibilities between modems from two different manufacturers. NOTE: When using 56K modems to communicate with remote access control networks, all modems must use the same communication format - either X2 or Flex. Incompatibilities between the two formats make some modems of one format incapable of reliable communication with modems of the competing format. Modems using the V.90 specification are compatible regardless of whether they are from an X2 or Flex manufacturer.

4.12.1


Direct Serial Connection – Controller to PC

If the host computer has a male DB-9 connector on the serial port, you must use a Keri Systems KDP-552 cable or create a cable according to the drawing in Section 4.12.1.1 on page 14.

Page 13 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
4.12.1.1 PC/DB-9F to PXL/TB-12 RS-232 Direct Serial Connection The Keri Systems part number for this cable is KDP-252. To use the KDP-252, cut off one end of the cable and wire it to the TB-12 connector as shown in Figure 15.

Figure 15: PC/DB-9F to PXL/TB-12 RS-232 Direct Serial Connections

Page 14 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
4.12.2 Modem to Controller
To make the connection between access control network and host computer you will use two cables: one between the host computer and its modem (see Section 4.12.3 on page 16), and one between the master controller and its modem. • • If the modem has a female DB-25 connector, you must use a Keri Systems KDP-336 cable or create a cable according to the drawing in Section 4.12.2.1. If the modem has a female DB-9 connector, you must create a cable according to the drawing in Section 4.12.2.2 on page 15. Modem/DB-25M to PXL/TB-12 Serial Port Connection

4.12.2.1

The Keri Systems part number for this cable is KDP-336. To use the KDP-336, cut off one end of the cable and wire it to the TB-12 connector as shown in Figure 16.

Figure 16: Modem/DB-25M to PXL/TB-12 Serial Port Connections 4.12.2.2 Modem/DB-9M to PXL/TB-12 Serial Port Connection

The Keri Systems part number for this cable is KDP-929M. To use the KDP-929M, cut off one end of the cable and wire it to the TB-12 connector as shown in Figure 17.

Figure 17: Modem/DB-9M to PXL/TB-12 Serial Port Connection

Page 15 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
4.12.3 Modem to PC Serial Connection
Keri Systems does not provide this cable. It is an off-the-shelf item from any computer supplier or electronics store, and its configuration is dependent upon the configuration of the serial port on the host computer. Based on the serial port, there are four possible cables. • • • • If the modem has a male DB-25 connector and the host computer’s serial port has a female DB-9 connector, purchase or create a cable according to the drawing in Section 4.12.3.1 on page 16. If the modem has a male DB-25 connector and the host computer’s serial port has a female DB-25 connector, purchase or create a cable according to the drawing in Section 4.12.3.2 on page 16. If the modem has a male DB-9 connector and the host computer’s serial port has a female DB-9 connector, purchase or create a cable according to the drawing in Section 4.12.3.3 on page 17. If the modem has a male DB-9 connector and the host computer’s serial port has a female DB-25 connector, purchase or create a cable according to the drawing in Section 4.12.3.4 on page 17. Modem/DB-25M to PC/DB-9F PC Serial COM Port Connection

4.12.3.1

Figure 18: Modem/DB-25M to PC/DB-9F PC Serial COM Port Connection 4.12.3.2 Modem/DB-25M to PC/DB-25F PC Serial COM Port Connection

Figure 19: Modem/DB-25M to PC/DB-25F PC Serial COM Port Connection

Page 16 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
4.12.3.3 Modem/DB-9M to PC/DB-9F PC Serial COM Port Connection

Figure 20: Modem/DB-9M to PC/DB-9F PC Serial COM Port Connection

4.12.3.4

Modem/DB-9M to PC/DB-25F PC Serial COM Port Connection

Figure 21: Modem/DB-9M to PC/DB-25F PC Serial COM Port Connection

Page 17 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 4.13 Alarm Control Panel to PXL-510 Connection
The PXL-510 controller’s TB-11 (see Figure 1 on page 1) provides a communication link between the NetworX NX-8E Alarm Control Panel and the PXL-510 master controller via the Serial Interface Cable (see Figure 22). • Keri Systems provides a serial interface cable. However, if you need to make your own, see the drawing in Section 4.13.1 on page 18.

Figure 22: PXL-510 Controller to NetworX NX-8E Alarm Control Panel Via the Serial Interface Cable

4.13.1

Serial Interface Cable/DB-9F to PXL-510/TB-11 Connection

The Keri Systems part number for this cable is KDP-552.

Figure 23: Serial Interface Cable/DB-9F to PXL-510/TB-11 Connection

Page 18 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

5.0

Powering The Controller for the First Time

NOTE: Verify the earth ground1 has been connected at pin 3 of TB-2 before turning the power on for the first time. NOTE: Do not connect the 12 VDC power supply’s terminal block output to the TB-2 connector on the PXL-500/PXL-510 controller until you have completed all the steps in section 5.1.

5.1
1. 2. 3. 4. 5. 6.

Verify the 12 VDC Supply Voltage
Set the DVM to a DC volt scale capable of reading 12 VDC. Turn the power supply ON. Place the Red DVM lead on the power supply’s terminal block output - Pin 1. Place the Black DVM lead on the power supply’s terminal block output - Pin 2. Check the DVM reading. It should read between +12 VDC to +14 VDC. If the DVM does not read between +12 VDC to +14 VDC, verify the power supply is of the correct voltage, verify the cable length does not exceed 200 feet, and verify the cable gauge is AWG 18. This problem must be corrected before power can be supplied to the controller. Turn the power supply OFF. Connect the power supply’s terminal block output to the TB-2 connector on the PXL-500/PXL-510 controller. The controller is now ready to be powered ON.

To verify the 12 VDC supply voltage:

7. 8. 9.

NOTE: On long power cable runs, keep in mind the resistance in the cable itself causes a drop in voltage at the end of the run. The power supply must be able to account for this voltage drop.

5.2

Verify the Wiegand Reader Supply Voltage

All Keri Systems proximity readers can use from 5 to 12 VDC power while some Wiegand compatible readers use only 5 VDC. For Wiegand configured PXL-500/PXL-510 controllers, there is a warning LED on the mother board to indicate if the controller is applying 12 VDC to the Wiegand compatible reader. If your Wiegand compatible reader does operate on 5 VDC no changes need to be made; the default position for the jumper is set to 5 VDC power. If your Wiegand compatible reader requires 12 VDC, turn the controller power off and move the jumper on JP5 (at the lower left-hand corner of the controller) from pins 2-3 to pins 1-2. When power is restored, the warning LED will turn on indicating 12 VDC is being supplied to the Wiegand compatible reader.

1. Ground wire is green with or without yellow tracer.

Page 19 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 5.3 RS-485 Wiring Test
The RS-485 wiring test is provided for field testing of the RS-485 connection. The RS-485 wiring test is done in two steps. The first step tests the negative side of the RS-485 (TB-1 pin 1 - see Figure 1 on page 1). The second step tests the positive side of the RS-485 (TB-1 pin 2). Make sure the RS-485 cable drain wire is connected to pin 3 on TB-1 on each controller in the network. NOTE: The RS-485 wiring test will show if there are any PXL-250s that still have the R45 resistor. This resistor must be removed for the RS-485 wiring test to work properly. For information on how to test a specific controller and remove the R45 (2.2K) resistor, refer to the R45 (2.2K) Resistor Removal Application Note (P/N 01736-001).

5.3.1
1. 2. 3. 4. • • • •

RS-485 Negative Test

Make sure all controllers are powered up. Install the jumper across pins 1-2 on JP9 on the master controller ONLY. LED11 will illuminate RED continuously (it is ok for the green LED to be either off or flashing). Check each slave unit on the system. The following guide will inform you of that controller’s status If LED11 is illuminated RED on every controller in the network, then the RS-485 negative wiring is ok. If LED12 is illuminated Green, then the + and - lines are reversed somewhere in the RS-485 wiring or at the controller. If no LED is illuminated, then there is an open wire somewhere in the RS-485 wiring, at the controller, or the drain wire. If both LEDs are illuminated on all controllers, then there is either a short in the wiring somewhere in the RS-485 wiring or at the controller, or there is one or more PXL-250s that still have the R45 resistor.

5.3.2
1. 2. 3. 4. • • • •

RS-485 Positive Test

Once all controllers on the network have been checked and are operating correctly, return to the master controller. Switch the jumper on JP9 from pins 1-2 to 2-3 on the master controller ONLY. LED12 will illuminate GREEN continuously (it is ok for the red LED to be either off or flashing). Check each slave unit on the system. The following guide will inform you of that controller’s status If LED12 is illuminated GREEN on every controller in the network, then the RS-485 positive wiring is ok. If LED11 is illuminated RED, then the + and - lines are reversed somewhere in the RS-485 wiring or at the controller. If no LED is illuminated, then there is an open wire somewhere in the RS-485 wiring, at the controller, or the drain wire. If both LEDs are illuminated on all controllers, then there is either a short in the wiring somewhere in the RS-485 wiring or at the controller, or there is one or more PXL-250s that still have the R45 resistor.

Once all controllers on the network have been checked and are operating correctly, return to the master controller. 5. 6. Remove the jumper from JP9 (be sure to keep the jumper in a place where it may be used in future tests). Either perform a reset on the master controller, or perform an Autoconfig in Doors. The test is complete and the system is in operating order.

NOTE: LEDs 11 and 12 blinking when not in RS-485 wiring test mode is normal.

Page 20 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 5.4 Resetting the Controller's RAM
If you're turning system power on for the first time or have just changed the EPROM/PIC, the PXL-500/PXL-510 controller's RAM must be reset before performing any other action. This clears any spurious information that may be in the RAM in preparation for entering your access control information. Before applying power, insert a jumper across pins 1 and 2 of JP10 on the controller. Hold the S1 Options Button down and turn the controller's power on. The beeper for the reader attached to the controller will beep as power comes on followed by a beep-beep indicating the controller's firmware has reset the controller's RAM. Release S1. If the optional Alpha/Numeric Display has been installed, it will display a “SYSTEM RESET” message. Turn system power off and remove the jumper on JP10. The controller is now ready to be powered up and receive information from Doors. NOTE: Resetting the system RAM completely erases all information within the PXL-500/PXL-510 controller. If there is any information in system RAM from an access control installation and the system RAM is reset, the information in the controller is lost and cannot be recovered.

5.5 5.6

Viewing the Controller's Address Setting the Controller's Address

To view the controller's address, click S1. The controller's address will appear on the address display for 2 to 3 seconds.

To set the desired operating address for the controller, verify the jumper to JP10 is NOT installed (if the jumper on JP10 is installed, the controller RAM will be reset when the power is turned on). Hold the S1 Options Button down and turn the controller's power on. The beeper for the reader attached to the controller will beep as power comes on. Release S1. The address display LEDs then become active and the controller's address can be set. If an Alpha/Numeric Display is connected to the controller, “ADDRESS CHANGE” will appear on the display. The address range is from 1 to 128 (the Master Controller must be set to address 1). Quickly double clicking S1 toggles between increasing and decreasing the controller address. The top LED character will display either a "+" or a "-" to show which direction is active. A single click of S1 changes the controller address by 1. If you're at address 128, a +1 click will roll the address over to 1; conversely, if you're at address 1 a -1 click will roll the address over to 128. Holding S1 down rapidly scrolls through the addresses. After the new address has been set, you must wait approximately 30 seconds after releasing the S1 button. There is a timer in the controller's firmware that assumes that after 30 seconds of inactivity (no address clicks), the entered address is the desired address for that controller. When the 30-second timer expires, there will be a beep-beep-beep from the reader indicating the controller has recognized and accepted the new address and the address LEDs will turn off. If an Alpha/ Numeric Display is connected to the controller, “UNIT ##” will appear on the display (where ## is the controller's address). To ensure the address change will be recognized by Doors, power down the controller. Then, after verifying the JP10 jumper is NOT installed (installing the JP10 jumper will reset the controller RAM when powering up), apply power to the controller. The controller is now ready to be used under the new address. NOTE: When the controller’s address is changed the RAM is automatically reset. A Total Update must be performed from Doors.

Page 21 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide 5.7 The Master Controller
The Master Controller must be set to address 1 so that all slave controllers on the access control network can identify the master controller. For the Master Controller to correctly identify all slave controllers on the network, one of two things must be done. 1. The master controller must be the last unit on the network to be powered on. This ensures that when the Master Controller begins polling the network to see what slave units are connected for system configuration, all slave units are already communicating their unique addresses and their configuration information. The Auto-Configuration routine within the Doors program must be run. This instructs the Master Controller to poll all controllers on the network for addresses and configuration information (the Auto-Configuration button is found under the Setup/System/Controllers tab).

2.

5.8

Reader Responses to Access Control Events

During day-to-day activity, the reader will respond to access control events in a specific manner. Table 3 provides a summary of the reader's LED and beeper actions during access control events. For information on reader responses to alarm controller access events, see the NetworX NX-8E Alarm Control Application Note (P/N 01919-001). Table 3: Reader Responses to Access Control Events Event waiting for an event access granted access denied door alarm door RTE Reader’s LED Status displays a steady Amber LED displays a Green LED until the door is closed or the door unlock time is reached flashes a Red LED flashing Red LED for the duration of the alarm condition displays a Green LED until the door is opened or the door unlock time is reached Reader’s Beeper Status silent one long Beep one short Beep pulsating Beep for the duration of the alarm condition one long Beep

Page 22 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide

6.0

General Information on Inputs

A controller input detects a state change generated by a device outside the controller that may prompt a response from the controller. Input devices that generate a state change may be normally closed or normally open. This section provides a brief description of normally closed versus normally open inputs.

6.1

Normally-Closed

A normally closed input device continually keeps a circuit active or complete. A state change is generated when the normally closed input device is forced open, breaking the circuit. In an access control system, a door switch is a typical example of a normally closed device. While the door remains closed, the switch remains closed. When someone opens the door, the door switch is opened, breaking the circuit and generating a state change. The controller then responds to the state change and generates an output (such as sounding an alarm if the door is a secure door).

6.2

Normally-Open

A normally open input device continually leaves a circuit open, or incomplete. A state change is generated when the normally open input device is forced closed, completing the circuit. In an access control system, a request-to-exit (RTE) button is a typical example of a normally open device. In an access control installation, an RTE button is located on the secure side of a door. While there is no one there pressing the button, the switch remains open. When someone desires to exit through a secure door, they press the RTE button, closing the circuit and generating a state change. The controller then responds to this state change and generates an output (such as unlocking the door to allow egress).

7.0
7.1

General Information on Safety versus Security with Door Locks
Fail-Safe Door Lock

When installing a door lock there are two things to consider: safety versus security, or should the door be "fail-safe" or "fail-secure."

Fail-safe means that if the power should fail at a door (perhaps due to a power outage or equipment failure), the door will automatically unlock allowing entrance or egress. Power is required to keep the door locked. A fail-safe door ensures people will be able to enter and exit a secured area through that door in the case of an emergency. A typical fail-safe application may use a magnetic lock. In this application, the controller energizes the lock relay, causing the lock relay to change its state. In its new state the normally closed circuit is opened breaking the power to the magnetic lock and allowing the door to be opened.

7.2

Fail-Secure Door Lock

Fail-secure means that if the power should fail at a door (perhaps due to a power outage or equipment failure), the door will automatically lock and not allow entrance but will continue to allow egress. Power is required to unlock the door. A fail-secure door ensures a secured area remains secure regardless of the situation. A typical fail-secure application may use a door strike. In this application, the controller energizes the lock relay, causing the lock relay to change its state. In its new state the normally open circuit is closed activating the release mechanism for the door strike on the door to be opened.

Page 23 of 24

P/N: 01918-001 Rev. A

PXL-500 / PXL-510 Tiger Controller
Quick Start Guide Contact Keri Systems:
Keri USA 2305 Bering Drive San Jose, CA 95131 Keri UK, Ireland, Europe Unit 17 Park Farm Industrial Estate Ermine Street Buntingford Herts SG9 9AZ UK Telephone: + 44 (0) 870 444 7234 Fax: Web: E-mail: + 44 (0) 1763 274 106 www.kerisystems.co.uk sales@kerisystems.co.uk tech-support@kerisystems.co.uk

Telephone: Fax: Web: E-mail:

(800) 260-5265 (408) 435-8400 (408) 435-7163 www.kerisys.com sales@kerisys.com techsupport@kerisys.com

End of document.

Page 24 of 24

P/N: 01918-001 Rev. A

Similar Documents

Free Essay

My Information

...Actions of all roadway users including pedestrians, animals, bicyclists, and other drivers impact your level of risk as a driver. To help manage risk, it is essential that you remain alert to conditions or objects that can increase levels of risk. Here is a checklist to help you manage risk: Conduct a thorough visual search. Search 30 seconds ahead of your path of travel for objects or conditions that could become a threat. Have a plan. Identify an alternate path of travel 15 seconds ahead, and the level of traction available in case of an emergency. Never tailgate. Always travel with an adequate cushion of space ahead of your vehicle. Position your vehicle with space to the sides and the front with an escape route, should you need it. Obey all traffic controls. Exercise the right-of-way rules. Drive defensively. Try to predict the possible actions of other highway users. Do not drive where you cannot see. If your vision is blocked, reduce your speed and reposition your vehicle so you can see well ahead, and around your vehicle; do not forget to look behind. See and be seen. Communicate your presence to other road users by always driving with your daytime running lights or low-beam headlights. Remember, if you cannot see them, they probably cannot see you. Look where you want your vehicle to go. Avoid distractions. Avoid sudden steering and braking movements. Be a considerate driver. Keep your vehicle in...

Words: 256 - Pages: 2

Free Essay

Conventional Accounting System and Information Technology: Experiences in My Places of Work.

...CONVENTIONAL ACCOUNTING SYSTEM AND INFORMATION TECHNOLOGY: EXPERIENCES IN MY PLACES OF WORK. BEING A SEMINAR PAPER PRESENTATION IN ACCOUNTING AND INFORMATION TECHNOLOGY FOR MASTERS IN ACCOUNTING (MAC) DEPARTMENT OF ACCOUNTING FACULTY OF ADMINISTRATION SCHOOL OF POSTGRADUATE STUDIES AHMADU BELLO UNIVERSITY, ZARIA, NIGERIA BY: KALU NNANNA NWONYUKU JUNE, 2013 CONTENTS 1.1.1 INTRODUCTION 1.2.1 THE MEANING OF ACCOUNTING AND ACCOUNTING PROCESS 1.2.2 THE ROLES AND FUNCTION OF ACCOUNTING INFORMATION 1.2.3 BASIC ELEMENTS OF AN ACCOUNTING INFORMATION 1.2.4 BASIC ACCOUNTING POSTULATES AND PRINCIPLES 1.3.1 MEANING OF INFORMATION TECHNOLOGY 1.3.2 ADVENT OF INFORMATION TECHNOLOGY IN ACCOUNTING SYSTEM 1.3.3. THE IMPORTANCE OF INFORMATION TECHNOLOGY TO ACCOUNTING SYSTEM 1.4.1 INFORMATION TECHNOLOGY USE FOR AN ACCOUNTING SYSTEM 1.4.2 SOFTWARE FOR ACCOUNTING INFORMATION SYSTEM 1.4.3 FACTORS TO CONSIDER WHEN CHOOSING ACCOUNTING SOFTWARE 1.4.4 HOW TO CHECK ACCOUNTING SOFTWARE 1.5.1 MERITS OF COMPUTERIZED ACCOUNTING SYSTEM 1.5.2 DEMERITS/LIMITATION...

Words: 12221 - Pages: 49

Free Essay

My Information

...Benefits of Fascism Fascism is a type of governance where the government controls politics, social behavior and economy. Under fascism political system, the individual rights of the people are greatly minimized, with the nation being glorified. Citizens are supposed to only work for the government and it is a system that promotes dictatorship. Below are key benefits of fascism. 1. Enhances security The military plays a vital role in a fascist system since it is required for protecting national security as well as fighting enemies. Most of the nation’s resources are given to the military in spite of domestic problems and policies. Fascism gives more significance to the state in contrast to the citizens’ rights and thus military productivity is a vital state interest. This leads to a better military, thereby increasing security. 2. Promotes patriotism Fascism is essential concerned with the protection of national agendas. Individual rights normally take second place, while national policies are provided first priority. Since patriotic symbols, flags and slogans can be seen everywhere, fascism encourages patriotism. The citizens will thereby be united so as to eliminate any perceived threat to the state. 3. Limits media Sometimes media are credited with reporting biased news that causes conflicts amongst the population. In the fascist system, the government has great control over mass media. There are very strict polices placed on media and the government typically...

Words: 1819 - Pages: 8

Premium Essay

New Document to Join

...(http://www.chevening.org/) Samuel Duah Ghana Chevening Scholarships Personal details Title Ms Please write your name as it appears or will appear on your passport Lastname Duah Firstname Samuel Other names Boadu Date of birth 6 July 1989 Country of citizenship Ghana In the majority of cases, to receive a Chevening Award, you must attend a face to face interview at the British Embassy or High Commission in this country. Is your country of residence different from your country of citizenship? No Do you hold Dual Citizenship? No Contact details Primary email address psamdb@ymail.com Additional email address psamdb@gmail.com Phone number 1 233246184325 Phone number 2 233242143956 Skype ID Please write your current postal address below. You do not need to write your country. First line of address Advent Reformed Institute Second line of address Post Office Box 198 Third line of address Kade- E/R Fourth line of address Your education Undergraduate education The Chevening programme requires applicants to have achieved an undergraduate qualification that is equivalent to at least an upper second-class (2:1) honours degree in the UK at the time they submit their application. Please provide details of your undergraduate degree below. You will have the opportunity to inform us of additional qualifications at a later point. Country of study Ghana University/college Kwame Nkrumah University of Science and Technology Date from August 2008 Date to May 2012 Degree type BSc Degree subject...

Words: 3424 - Pages: 14

Premium Essay

Persuasive Essay On Death Donation

...The soft beeps of my alarm clock bring me out of my slumber almost immediately, causing a slight jolt to erupt from my body as I sit up in bed. With my eyes half closed, my arm juts out and fumbles with the various objects on my end table until it finally hits that sweet spot on the small, yet loud, box keeping me from sleeping any longer. A light groan escapes my lips, followed by a quick yawn. Sundays are always considered to be the worst, in my own subjective opinion. I stretch my arms out of either side of my body as my legs swing to the right and off of my bed. I give my legs a moment to relax, my hands finding themselves by my hips before finally pushing me off of the bed and onto my feet. As per usual, I trudge out of my room and into...

Words: 1789 - Pages: 8

Free Essay

Gdfhjgh

...instructed otherwise.) Not only is a topic sentence the first sentence of a paragraph, but, more importantly, it is the most general sentence in a paragraph. What does "most general" mean? It means that there are not many details in the sentence, but that the sentence introduces an overall idea that you want to discuss later in the paragraph. For example, suppose that you want to write a paragraph about the natural landmarks of your hometown. The first part of your paragraph might look like this: My hometown is famous for several amazing natural features. First, it is noted for the Wheaton River, which is very wide and beautiful. Also, on the other side of the town is Wheaton Hill, which is unusual because it is very steep. (Notice how the first sentence begins with "My hometown..." a few spaces to the right of the paragraph edge. This is an indentation. All paragraphs in English MUST begin with an indentation.) Note how the first sentence, My hometown, Wheaton, is famous for several amazing geographical features,is the most general statement. This sentence is...

Words: 1777 - Pages: 8

Free Essay

Business

...Kimberly Tucker, Chris Salt, Ashley Solomon Case 7: Mattel: Overcoming Marketing and Manufacturing Challenges 11/01/2010 Marketing Management 6800 Section 004 The Problem: The problem surrounding Mattel Inc., one of the world’s largest toy companies, is their mismanagement of international subcontractors and vendors and the production of certain toys (the manufacturing process), as well as their inability to adapt their marketing strategy or product to the constantly changing “demographic and socioeconomic trends” (Ferrell, et. all 466). This is supported by Mattel’s legal battle with Carter Bryant and MGA, their forced recall of certain toys that were manufactured overseas, and the increasing rate at which traditional toys are becoming less appealing to today’s young audience. Essentially, Mattel’s mismanagement and oversight lead to violations in terms of ethical and social responsibilities and safety standards. Issues Relevant to the Problem: Mattel’s problem of mismanagement can be divided into several issues that need to be considered: legal issues, international supply chain issues, and an increase in technology-based toys. In regards to legal issues, Mattel has been involved in prolonged litigation with Carter Bryant and MGA over a breach of an employment contract and copyright infringement. Due to Mattel’s poor management of its overseas manufacturers, in which unauthorized subcontractors and third-party suppliers were hired and unsafe materials used, several...

Words: 3390 - Pages: 14

Premium Essay

Demographic Information: Impact On My Development

...Demographic Information 1. I was born on November 13, 1998. Having been born during a technological era, I have a better knowledge and background in our rapidly changing technology based world. This made an impact on my development because I am able to research and learn through technology. 2. My parents, Donnie and Laura Bailey, have been married for twenty-one years. My mom is fifty-two years old and my dad is fifty-one years old. My parents have impacted my development by teaching me many important life lessons. Together my parents have demonstrated an authoritative parenting style. This style of parenting has impacted my development because it has taught me to be a responsible, caring person. 3. In my family, I have three older siblings who have been major role models in my life. My sisters, Chantelle (thirty-one years old) and Madyson (twenty years old) have taught me many important lessons. My brother Timmy passed away in 2010, at the age eighteen. The loss of my brother has had a huge impact on my life and taught me about the difficult grieving process. 4....

Words: 671 - Pages: 3

Premium Essay

Growing Up In A Foster Home-Personal Narrative

...Cornell, that's pretty nice.” She replied smirking “Haha yeah. It's almost like a tradition in my family to go there. How about you?” “I went to New York University and studied law. It's actually a tradition in my family to go to Cornell too. I grew up in a foster home most of my life and didn’t learn about the tradition until recently when I was digging into my birthparents past and stuff.” Kamberly replied. “I grew up in a foster home too. Maybe that's where we have seen each other. Where did you grow up?” he asked “I’ve grown up here, in New York for my whole life. Never lived anywhere else. How about you?” “Oh, that can’t be it then. I grew up in Washington most of my life.” he replied “Weird question, but what’s your last name?” she asked. She had a feeling that she needed to ask that question. She didn’t know why it just kept nagging at her mind. “Arrowmen.” She felt her jaw drop and her eyes widen. She couldn’t believe it. The hair, the eyes, the smile. It all seemed too familiar. She had known there was a possibility that she had siblings, but she never put much thought into it. “That my last name.” she replied quietly. His eyes started watering. He couldn’t meet her...

Words: 881 - Pages: 4

Free Essay

Someone Who Influenced My Life

...Why would an author of a book influence me so much? It is because Daniel Quinn has written "My Ishmael" in such a beautiful way that what he's thinking comes across to you like as though you're having a conversation in person with him. He uses a talking Gorilla as a means to convey his points of view on how the world is in a degenerative mode and though I felt this strange at first, it became clear later as to why he used a Gorilla in the first place. The Gorilla here represents nature's voice and is a reminder that we need to look for ways to communicate with nature, first hand. This was the first eye opening aspect from the author. The second was the author's penchant for coming up with brilliant stories to derive and communicate his point to the reader. Instead of driving in his philosophies by pure theory would have been boring and heavy, but the author uses wonderful and thought provoking stories to do the same, so effectively. The first was the simple concept of food kept under lock and key. This is a practice that comes so naturally to us, but he brings out why this is a very unnatural way of things. For early man, what grew in the world belonged to everyone in the society, and to put it under lock and key is to basically create a working class who will do tasks, useful or useless, in order to earn their bread. Ishmael's (the name of the gorilla) teachings turn toward the subject of formal education, which he argues is merely a way to keep children out of the work...

Words: 593 - Pages: 3

Free Essay

Mattel and Its Challenges

...The Problem: The problem surrounding Mattel Inc., one of the world’s largest toy companies, is their mismanagement of international subcontractors and vendors and the production of certain toys (the manufacturing process), as well as their inability to adapt their marketing strategy or product to the constantly changing “demographic and socioeconomic trends” (Ferrell, et. all 466). This is supported by Mattel’s legal battle with Carter Bryant and MGA, their forced recall of certain toys that were manufactured overseas, and the increasing rate at which traditional toys are becoming less appealing to today’s young audience. Essentially, Mattel’s mismanagement and oversight lead to violations in terms of ethical and social responsibilities and safety standards. Issues Relevant to the Problem: Mattel’s problem of mismanagement can be divided into several issues that need to be considered: legal issues, international supply chain issues, and an increase in technology-based toys. In regards to legal issues, Mattel has been involved in prolonged litigation with Carter Bryant and MGA over a breach of an employment contract and copyright infringement. Due to Mattel’s poor management of its overseas manufacturers, in which unauthorized subcontractors and third-party suppliers were hired and unsafe materials used, several toy products were recalled. Advances in technology and changes in socioeconomic and demographic trends have created marketing, privacy, and product development issues...

Words: 3368 - Pages: 14

Premium Essay

Mattel

...Case 1 Marketing Strategy Jasmine Hall Mattel 1. Yes, Manufacturers of children’s products have a special obligation to not mislead consumers and society. One responsibility to the society that Mattel is performing is their commitment to protecting the privacy of their online customers when visiting their website or purchasing a product online. By assuring parents that their children’s privacy will be respected, Mattel demonstrates that that is takes its responsibility of marketing to children very seriously. They are also responsible for product safety, quality, protecting the environment, customs, evaluation and monitoring and compliance. Mattel’s business partners must have high standards for product safety and quality, adhering to practices that met Mattel’s safety and quality standards, which have been seriously violated in the past. Also, because of the global nature of Mattel’s business and its history of leadership in this area, the company insists that business partners strictly adhere to local and international customs laws. Partners must comply with all import and export regulations. The company also seeks to maintain an independent monitoring system that provides checks and balances to help ensure that standards are met. If certain aspects of Mattel’s manufacturing principles are not met, Mattel will try to work with contractors to help them fix their problems. New partners will not be hired unless they meet Mattel’s standards. If corrective action is advised...

Words: 692 - Pages: 3

Free Essay

Time Capsel

...Greetings from the past! If you are reading my letter then that means you have found the time capsule that we have left for you. I am hopeful that you will enjoy the new information you learn from me. My name is Brandy Taylor, I am writing this to give you my perspective and my knowledge of my present life and the society that I currently live in here in 2013. My hope is that with the information I tell you, you will gain a better understanding of how life is for me and my family during this time. A brief description of me is that I am a single mother of three amazing children that are currently ages 20, 15 & 13. I am in my late 30’s and live a very healthy lifestyle that does not make me look my age. My children and I currently reside in Dallas, Texas, where the summers are hot and the winters are mild. I am currently employed for an audio/visual, lighting company called LMG, Inc. as an Administrative Assistant this is at least until I finish college. My current work schedule is Monday through Friday 8:00am to 5:00pm, with weekends and major holidays off. Also, I am currently enrolled in college at Kaplan University with one term left till I earn my Bachelors Degree in Business Administration with a career focus of Human Resource Management. Although I am satisfied with my current job it is my goal to obtain a position in my dream career of Human Resources; this is a passion for me. My current week consists of working till 5:00pm, dinner with the kids, doing some class...

Words: 1792 - Pages: 8

Free Essay

Jody's Popcorn Case Answers

...Easter and Christmas. If they have some way of knowing your birthday, that too would be an appropriate time. It really depends on if they have some way of getting more information on the corporation that could provide insight to a corporation. For example for a college, possibly after first semester and the school year would be a good time to promote Jody’s as a good gift for all of Carthage’s staff. 2. From what I gathered in the article, it seems you can really target any type of business. I say this due to the diversity between just holidays, as well as University’s and professional sport’s teams. This widens the reach of the product drastically in my eyes. Possibly if they could purchase an ad in a popular business magazine, with possible promotional code to get people to check out their website. Also they should maintain their social media marketing as well. 4. The first thing I notices is how much more user friendly is then the other premium popcorn sites. The only one that came close to Jody’s was the popcorn factory. I also noticed that Jody’s had their contact information right on top of the page so you can’t miss it. There is nothing worse than having to search to find a companies contact information. I like how the show a nice amount of pictures on the opening page and then more information if you pick on a selected product. A lot of the websites were way to wordy. In the brief time I spent on these sites the only real disadvantage I may have saw was...

Words: 342 - Pages: 2

Free Essay

Cougar

...can’t put it into words. James might be able to; he might be able to give you a taste of his life. All I can say is… well… to me, James is a friend, but to the world, he’s a hero. Chapter 1 I’m going to try to explain this to you, my story. A lot of the stuff that happens here is horrible, but it is the truth. I wouldn’t lie. You may not understand a lot of it. That’s normal. Let’s see if I can remember where it all started… It was in January when I was recruited. That whole month blurred together. I don’t remember much of it. I started the brutal training in February. Let’s just say that it was about 2 degrees shy of hell. We were pushed to the limit. They had mock prisons where they would torture us and see if we could hold up. One time we had to swim through blood. Nothing will ever be able to describe it. About 6 months after the grueling training ended I was assigned to my first mission. It was a black ops mission and I was going in solo. A black ops mission means that if I died or was captured, the military would deny that I had any participation with them. For some reason though, I didn’t care if I died. If I died, I died. No fear, no regrets. No one even cared if I died so why should I? Finally I got my task. I was...

Words: 2672 - Pages: 11