Free Essay

Heat Exchanger Design

In:

Submitted By gokcesgr93
Words 6124
Pages 25
Design of heat exchangers required for a 50-100kW superheated Rankine cycle
MECH 421

Huzeyfe SHAHIN
Gokce SAGIR
Usman Arshad SHAH
28th December 2015

Table of Contents
1.

ABSTRACT .............................................................................................................................................. 3

2.

INTRODUCTION ..................................................................................................................................... 3

3.

LITERATURE REVIEW ............................................................................................................................. 3

4.

SIMPLE DESIGN ..................................................................................................................................... 3
4.1 Evaporator at 800 kPa (Counter Flow) ................................................................................................ 4
4.1.1 Preheater ..................................................................................................................................... 4
4.1.2 Boiler ............................................................................................................................................ 4
4.1.3 Superheater ................................................................................................................................. 5
4.2

Evaporator at 800 kPa (Shell & Tube) ........................................................................................... 5

4.3 Evaporator at 650 kPa (Counter Flow) ................................................................................................ 7
4.3.1 Preheater ..................................................................................................................................... 7
4.3.2 Boiler ............................................................................................................................................ 7
4.3.3 Superheater ................................................................................................................................. 8
4.4 Evaporator at 650 kPa (Shell & Tube) ................................................................................................. 8
4.5 Condenser (Counter Flow) .................................................................................................................. 9
4.6 Condenser (Shell & Tube) ................................................................................................................. 11
5.

RATING ................................................................................................................................................ 12
5.1 Evaporator at 800 kPa (Counter Flow) .............................................................................................. 12
5.2 Evaporator at 650 kPa (Counter Flow) .............................................................................................. 14
5.3. Condenser (Counter Flow) ............................................................................................................... 16
5.4. Conclusion ........................................................................................................................................ 17

6.

REFERENCES ........................................................................................................................................ 18

1. ABSTRACT
The report focuses on a superheated ORC for the power plant capacity of 50 to 100 kW using R245fa. Design of all heat exchangers for the cycle are made. The report is divided into simple design and rating to identify the design conditions (diameter, length etc.). The rating part shows the effect on output temperatures, pressure drops and work outputs by changing the mass flow rate of the working and the outer fluid. Furthermore simple design of both counter flow and shell & tube type heat exchangers have been discussed.
2.

INTRODUCTION

Today, 69.3% of the electricity is generated by different types of steam generators, all of which rely on the application of Heat
Exchangers[5]. The aim of this project is to take a closer look at these heat exchangers, and accordingly, design a super-heated
Rankine cycle with a capacity of 50 to 100 kW. According to the literature review, it is found that the most suitable system to fit into this capacity range is Organic Rankine
Cycle (ORC).
3.

LITERATURE REVIEW

Organic Rankine Cycle is a well-known and widely spread thermodynamic cycle that converts heat into work. The heat is applied externally on a closed loop that uses one of the organic fluids such as R11, R123, R113,
R114, R245fa, R245ca, R236fa, and R134a as working fluid [4].
For the capacity range of this project, geothermal sourced Organic Rankine cycle is the optimum solution. Also, it is beneficial for environment since a boiler is not needed in this process and there will be no emission formed.

In geothermal resourced ORC, hot water vapor with temperature between 150°C and 230°Cis used to heat the working fluid to obtain energy, and the condensing fluid with approximately
10°C inlet temperature is used to condense the working fluid coming out of the turbine [1].
According to the performance test for a 100 kW
Organic Rankine Cycle using low temperature geothermal resources, the refrigerant mass flow rate should be 5 kg/s for an ORC designed for
113.1 kW with 9.74 cycle efficiency. This test appeared that the maximum power output for such a system was 91.22 kW with the cycle efficiency of 7.14 % and the measured refrigerant mass flow rate was 4.17 kg/s. The working fluid used for this test was R245fa [1].
On the other hand, one American based company (Infinity Turbine) claims that for a 50 kW Organic Rankine Cycle the mass flow rate of working fluid (R245fa) should be between
7.57 kg/s and 9.46 kg/s. Also, the mass flow rate of cooling fluid should be above 22.7 kg/s. The company also indicates that the dimensions for the cycle should be 92 cm x 152 cm x 183 cm
[2].
Furthermore, for an ORC with a pump efficiency of 40 %, aerodynamic turbine efficiency of 80 %, mechanical turbine efficiency 95% and electrical generator efficiency of 96%, the acceptable or expected pressure drop is 2% [3].
4. SIMPLE DESIGN
Organic Rankine Cycle running with geothermal resource: This part of the project focuses on the size of the heat exchanger. It is decided to have two different heat exchanger designs for two different pressure values (i.e. Counter flow at
800 kPa and 650kPa). The later part consists of the design of the condenser using counter flow type heat exchanger.
(Refrigerant: R245fa)

4.1 Evaporatorat 800 kPa(Counter Flow)
For the geothermal side Nusselt number calculation, the Dittus-Boelter equation for cooling was used from which ho was obtained as: ho =88862.6 W/m2K

 Q = 313.592 kW ε= Q/Qmax = 0.91
NTU =

By using the Dittus-Boelter equation again for heating this time, Nu was calculated for a phase changing fluid (R-245fa at 800kPa) from which hi was obtained as:

A=

d

ln ( do ) ∗ di
1 1
1
i
= + R f,ref +
+ R f,wat +
U hi
2k al ho  U=513.21 W/m2K
Th,i=Twat,i: 85.54°C Th,o=Twat,o: 77.962°C
Tc,i=Tref,i: 30°C Tc,o=Tref,o: ? mh: 9.9 kg/s
CP,h: 4.180 kJ/kg.K

mc: 4.17 kg/s
CP,c: 1.488 kJ/kg.K

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K
Cc = mc * CP,c = (4.17 kg/s)*(1.488 kJ/kg.K)
= 6.205 kW/K
Cmin = Cc = 6.205 kW/K
Cmax = Ch = 41.382 kW/K
C* = Cmin/Cmax = 0.15
Qmax= Cmin(Th,i - Tc,i) = 344.6 kW
Q = Qc = Qh = mc* CP,c(Tc,o - Tc,i ) = mh *
CP,h (Th,i - Th,o)
 Tc,o = 80.54°C
Q = Qc = Qh = mh * CP,h (Th,i - Th,o)

NTU ∗ Cmin
U

A = 32.16 m2
And then the required L and ΔPlosscan be calculated as:
L=

hi = 618.28 W/m2K
Then the overall heat transfer coefficient can be calculated as:

1 ε − 1) ln ( ∗
)
−1
C ε−1

 NTU = 2.66

P:800 kPa di:100 mm do: 110 mm D:130mm kaluminium:240W/mK Rf,ref:0.0002 Rf,wat:0.0001

4.1.1 Preheater



A
= 102.38 m πdi 1
∆ = ( ) ( 2 ) = 0.418

2

4.1.2 Boiler
By using the Kandlikar correlations, Nu was calculated for a phase changing fluid (R-245fa at
800kPa) from which hi was obtained as: hi = 2322.16 W/m2K
Then the overall heat transfer coefficient can be calculated as: d ln ( do ) ∗ di
1 1
1
i
= + R f,ref +
+ R f,wat +
U hi
2k al ho  U=1312.78 W/m2K
Th,i=Twat,i: 95.87°C Th,o=Twat,o: 85.54 °C
Tc,i=Tref,i: 80.54°C Tc,o=Tref,o: 80.54°C mh: 9.9 kg/s

mc: 4.17 kg/s

hfg,ref= 152.060 kJ/kg
CP,h: 4.180 kJ/kg.K

CP,c: ∞

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K
Cc = ∞
Cmin = Ch = 41.382 kW/K
Cmax = Cc = ∞

C* = Cmin/Cmax = 0
Qmax= Cmin(Th,i - Tc,I) = 634.09 kW

Cc = mc * CP,c = (4.17 kg/s)*(1.208 kJ/kg.K)
= 5.035 kW/K
Cmin = Cc = 5.035 kW/K

Q =Qc=Qh=mc(hfg)=mh*CP,h (Th,i - Th,o)

Cmax = Ch = 41.382 kW/K

 Q = 427.282 kW

C* = Cmin/Cmax = 0.12

ε= Q/Qmax = 0.674
1
ε − 1)
NTU = ∗ ln ( ∗
)
−1
C ε−1
 NTU = 1.12

Qmax= Cmin(Th,i - Tc,i) = 828.683 kW
Q = Qc = Qh = mc* CP,c(Tc,o - Tc,i ) = mh *
CP,h (Th,i - Th,o)
 Tc,o = 89.87°C

NTU ∗ Cmin
A=
U

Q = Qc = Qh = mh * CP,h (Th,i - Th,o)
 Q = 46.956 kW

A = 35.318 m2
And then the required L and ΔPlosscan be calculated as:
A
L=
= 112.42 m πdi ∆

ε= Q/Qmax = 0.57
NTU =

By using the Dittus-Boelter equation for heating this time, Nu was calculated for a phase changing fluid (R-245fa at 800kPa) from which hi was obtained as:

A=

d

NTU ∗ Cmin
U

A = 7.15 m2
And then the required L and ΔPlosscan be calculated as:
L=

hi = 769.87 W/m2K
Then the overall heat transfer coefficient can be calculated as:

1 ε − 1) ln ( ∗
)
−1
C ε−1

 NTU = 0.871

1
= ( ) ( 2 ) = 0.477

2

4.1.3 Superheater



A
= 7.15 m πdi 1
∆ = ( ) ( 2 ) = 2.428

2

ln ( do ) ∗ di
1 1
1
i
= + R f,ref +
+ R f,wat +
U hi
2k al ho The total values are as follows:

 U=613.49 W/m2K

L= 237.54 m

Th,i=Twat,i: 97°C Th,o=Twat,o: 95.87 °C Tc,i=Tref,i:
80.54°C Tc,o=Tref,o: ? mh: 9.9 kg/s
CP,h: 4.180 kJ/kg.K

mc: 4.17 kg/s
CP,c: 1.208 kJ/kg.K

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K

Q= 787.83 kW

ΔPloss= 3.32 kPa

4.2 Evaporator at 800 kPa (Shell & Tube)
Shell and tube heat exchangers are widely used types of heat exchangers due to the flexibility they provide to the designer for a wide range of pressure and temperature, and also, for limited

space that the heat exchanger is supposed to fit for some applications.

=

The correlations used for shell and tube heat exchanger design are as follows; = (0.4) = 0.543 = − ,0 = 0.028 . . =
= 0.1472


= 67.25/2

=
4[
=

2
2 √3

− 8,0 ]
4

(. ,0 /2)

= 0.0795

Where dt,0 represents the outer diameter of the tube, PT represents tube pitch and equal to
1.25dt,0, C represents clearance, As represents bundle cross-flow area, DS represents inside diameter of the shell, GS represents equivalent shell diameter and B is baffle spacing.

. 0.55 . 1/3 0.14
)
(
) ( )
( )

2
= 749.4/
= 0.36 (

Where ho is heat transfer coefficient for heating water, µ is dynamic viscosity of the water Cp is the specific heat of water, k is the thermal conductivity of the water.
The heat exchanger is designed according the triangular pitch and single pass tubes. Therefore;

=

()2 ,0

= (0.637) (
)(
)

2

= (785) (

2

)(
) = 79

()2 2
,

Where PR is the pitch ratio, △Tlm,cf is the log mean temperature difference, △Tm mean temperature difference, Af is the fouled area, Ac is clean area, and Nt is the number of tubes.
For the design of the shell and tube heat exchanger, three parts, pre-heater, boiler and super-heater, are examined separately By fixing overall length and shell diameter ratio, and by iterating the shell diameter, optimum length values are obtained, for each of the parts and overall length is fixed as 6.6 m for the assumed value of Ds as 1.328 m. Also, surface over design is found for all parts by Af/Ac as 1
Pressure drop for shell side: 0.16 kPa
Pressure drop for tube side: 4.74 kPa
The following formulas was used to calculate pressure drop formulas for shell side and tube side. = exp(0.576 − 0.19 ∗ ln()) = ⁄ =

CTP = 0.90

∆, =

,0

∆ =

∆1 − ∆2


ln (∆1 )
2

= 0.9 => ∆ = (0.9)(∆, )



2

CL = 0.87

=

. ∆

∆ = (

−1

∗ 2 ∗ ( + 1) ∗
2 ∗ ∗ ∗ ∅

4 ∗ ∗ ∗ ∗ 2
+ 4 ∗ ) ∗

2

4.3Evaporatorat 650 kPa(Counter Flow)

Q = Qc = Qh = mh * CP,h (Th,i–Th,o)

For the geothermal side Nusselt number calculation, the Dittus-Boelter equation for cooling was used from which ho was obtained as:  Q = 257.447 kW

ho =88862.6 W/m2K
P:650kPa di:100 mm do: 110 mm D:130mm kaluminium:240W/mK Rf,ref:0.0002 Rf,wat:0.0001

ε= Q/Qmax = 0.89
NTU =



 NTU = 2.47
A=

4.3.1 Preheater
By using the Dittus-Boelter equation again for heating this time, Nu was calculated for a phase changing fluid (R-245fa at 800kPa) from which hi was obtained as:

d

ln ( o ) ∗ di
1 1
1
di
= + R f,ref +
+ R f,wat +
U hi
2k al ho  U=502.42W/m2K
Th,i=Twat,i: 77.42°C Th,o=Twat,o: 71.19°C
Tc,i=Tref,i: 30°C Tc,o=Tref,o: ? mh: 9.9 kg/s
CP,h: 4.180 kJ/kg.K

mc: 4.17 kg/s
CP,c: 1.455 kJ/kg.K

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K
Cc = mc * CP,c = (4.17 kg/s)*(1.455 kJ/kg.K)
= 6.069 kW/K
Cmin = Cc = 6.069 kW/K
Cmax = Ch = 41.382 kW/K
C* = Cmin/Cmax = 0.15
Qmax= Cmin(Th,i–Tc,i) = 287.8 kW
Q = Qc = Qh = mc* CP,c(Tc,o–Tc,i ) = mh * CP,h
(Th,i–Th,o)
 Tc,o = 85.60°C

NTU ∗ Cmin
U

A = 29.85 m2
And then the required L and ΔPlosscan be calculated as:

hi =602.67 W/m2K
Then the overall heat transfer coefficient can be calculated as:

1 ε − 1) ln ( ∗
)
−1
C ε−1

L=

A
= 95.028 m πdi 1
∆ = ( ) ( 2 ) = 0.378

2

4.3.2 Boiler
By using the Kandlikar correlations, Nu was calculated for a phase changing fluid (R-245fa at
800kPa) from which hi was obtained as: hi = 2293.34 W/m2K
Then the overall heat transfer coefficient can be calculated as: d ln ( do ) ∗ di
1 1
1
i
= + R f,ref +
+ R f,wat +
U hi
2k al ho  U=1309.97 W/m2K
Th,i=Twat,i: 88.39°C Th,o=Twat,o: 77.42 °C
Tc,i=Tref,i: 72.42°C Tc,o=Tref,o:72.42°C mh: 9.9 kg/s

mc: 4.17 kg/s

hfg,ref= 158.540 kJ/kg
CP,h: 4.180 kJ/kg.K

CP,c: ∞

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K
Cc = ∞
Cmin = Ch = 41.382 kW/K

Cmax = Cc = ∞
C* = Cmin/Cmax = 0
Qmax= Cmin(Th,i–Tc,I) = 661.11 kW

Ch = mh * CP,h = (9.9 kg/s)*(4.180 kJ/kg.K)
= 41.382 kW/K
Cc = mc * CP,c = (4.17 kg/s)*(1.208 kJ/kg.K)
= 5.035 kW/K

Q =Qc=Qh=mc(hfg)=mh*CP,h (Th,i–Th,o)

Cmin = Cc = 5.035 kW/K

 Q = 454.201 kW

Cmax = Ch = 41.382 kW/K

ε= Q/Qmax = 0.687
NTU =



1 ε − 1) ln ( ∗
)
−1
C ε−1

 NTU = 1.16
A=

NTU ∗ Cmin
U

A =36.696 m2
And then the required L and ΔPlosscan be calculated as:
L=

A
= 116.81 m πdi 1
∆ = ( ) ( 2 ) = 0.479

2

C* = Cmin/Cmax = 0.12
Qmax= Cmin(Th,i–Tc,i) = 88.52kW
Q = Qc = Qh = mc* CP,c(Tc,o–Tc,i ) = mh * CP,h
(Th,i–Th,o)
 Tc,o = 85.6°C
Q = Qc = Qh = mh * CP,h (Th,i–Th,o)
 Q = 66.38 kW ε= Q/Qmax = 0.75
NTU =



 NTU = 1.469
A=

4.3.3 Superheater
By using the Dittus-Boelter equation for heating this time, Nu was calculated for a phase changing fluid (R-245fa at 800kPa) from which hi was obtained as:

And then the required L and ΔPlosscan be calculated as:
L=

d

NTU ∗ Cmin
U

A = 12.38 m2

hi = 745.18 W/m2K
Then the overall heat transfer coefficient can be calculated as:

1 ε − 1) ln ( ∗
)
−1
C ε−1

A
= 39.39 m πdi 1
∆ = ( ) ( 2 ) = 5.2

2

ln ( do ) ∗ di
1 1
1
i
= + R f,ref +
+ R f,wat +
U hi
2k al ho The total values are as follows:

 U=597.7 W/m2K

Q= 778.03 kW

Th,i=Twat,i: 90°C Th,o=Twat,o: 88.39 °C Tc,i=Tref,i:
72.42°C Tc,o=Tref,o: ? mh: 9.9 kg/s
CP,h: 4.180 kJ/kg.K

mc: 4.17 kg/s
CP,c: 1.208 kJ/kg.K

L= 251.23 m
ΔPloss= 6.07kPa

4.4 Evaporator at 650 kPa (Shell & Tube)
Similarly like before in order to decrease the length of the evaporator, Shell & Tube must be used. ℎ
1/3

0.55

.
)

= 749.4/2
= 0.36 (

(

.
)

(

0.14

)

.(

)

The following formulas was used to calculate pressure drop formulas for shell side and tube side. = exp(0.576 − 0.19 ∗ ln())

The heat exchanger is designed according the triangular pitch and single pass tubes. Therefore;

= ⁄

CL = 0.87

=

CTP = 0.90 =
∆, =

∆ =

,0

∆1 − ∆2

4 ∗ ∗ ∗ ∗ 2
+ 4 ∗ ) ∗

2

∆1
)
∆2

= . ∆



()2 ,0

= (0.637) (
)(
)

2

2

= (785) (

∗ 2 ∗ ( + 1) ∗
2 ∗ ∗ ∗ ∅

ln (

= 0.9 => ∆ = (0.9)(∆, )

=

∆ = (

−1

2

)(
) = 82

()2 2
,

Where PR is the pitch ratio, △Tlm,cf is the log mean temperature difference, △Tm mean temperature difference, Af is the fouled area, Ac is clean area, and Nt is the number of tubes.
For the design of the shell and tube heat exchanger, three parts, pre-heater, boiler and super-heater, are examined separately By fixing overall length and shell diameter ratio, and by iterating the shell diameter, optimum length values are obtained, for each of the parts and overall length is fixed as 6.8m for the assumed value of Ds as 1.357 m. Also, surface over design is found for all parts by Af/Ac as 1%.
Pressure drop for shell side: 0.15 kPa
Pressure drop for tube side:13.16 kPa

4.5Condenser (Counter Flow)
The flow that comes from the turbine to the condenser is still in vapor form, 150KPa and
40°C. To have the perfect situation, fully liquid flow at saturation temperature, mass flow rate of the coolant water has to be calculated. For this purpose, whole process divided into two parts, first one is cooling through saturation temperature, and second one is phase change process. The regions and the pinch point temperature difference can be seen in figure1. In addition to that, PPTD was assumed to be 5°C.
By knowing the inlet and outlet temperatures of the cooling water during phase change operation and the heat rejected during phase change from refrigerant fluid, mass flow rate of the cooling water for this perfect case can be determined.
During the whole design procedure, wall thickness assumed to be very small and effects of fouling was neglected. By using try-error method, at the end of the calculations diameters of the tubes was determined to have 2-3 percent pressure loss during whole condensation process. UA2(cooling region)=5,08 KW/K;
To find the required lengths, U has to be determined for both regions. For outer flow
(cooling water) by using Dittus-Boelter equation it was found as; ho =19.3 KW/m2K
“hi” was calculated by using the Dittus-Boelter formula for cooling region; for phase change region following equation was used. Nusselt number for phase change region;
Figure I di=120mm; do=130mm; mref=4,17kg/s;
PPTD=5°C;
P=150KPa;
Twat,in=10°C;
Tref,in=40°C;
Tsat=25.1°C; hfg,ref=160kj/kg; cwat=4,182 kj/(kg*K); cref,g=0,86 kj/(kg*K);
From equality of [mref* hfg,ref= mwat * cwat*(Tsatref-pptd-Twatin)]; mwat found as
15,79 kg/s.
Now, by knowing the mass flowrates, c values, it is possible to calculate UA values for first and second region to calculate total length and total pressure loss. Total heat rejected from the cycle can also be calculated at that step. To determine
UA values, E-NTU method was used just like the boiler design.
Q1= mref* cref,g*(Tref,in-Tref,sat)
Q2=mref* hfg,ref
Qtot,out=Q1+Q2=720KW
For a cycle with 50-100 KW output, this amount of heat rejection seems to be not acceptable but after subtracting this value from Qtot,in; it will give an acceptable work output.
While using the E-NTU method, in the first region Cr will be zero and cmin will equal to mwat*cwat. For the second region, cooling region, mref*cref will be cmin. This mref*cref will be equal to infinity during phase change process. For the formulas that was given in the previous parts for counter flow;
UA1(phase change region)=73KW/K;

Surface temperature was assumed to be constant and it equals to average cooling water temperature during phase region. hi,phase =0,86 KW/m2K hi,cooling =0,45 KW/m2K
U1=0,82KW/K(phase change)
U2=0,44KW/K(cooling)
Length of cooling section is 30,44m;
Length of phase change section is 234,84m;
Total length is 265,30 meters
Also, pressure drop for the tube that refrigerant flows, has to be calculated separately for phase change and cooling parts. 1
∆ = ( ) ( 2 ) 2
This formula can be directly used for cooling section and it says that pressure loss during cooling section equals to 3,46KPa.
For simple design part, at the entrance point of the phase change quality was 1 and at the exit quality was zero. So average quality was calculated and all the values was calculated by using it. Density, viscosity, average velocity etc.

= ∗ ∗ ∗

For phase change region pressure loss was calculated as 0,73KPa.
Then total pressure loss equals to 4,18KPa which meets with our limit.

= (1.58 ∗ ln() − 3.28)−2

=

4.6 Condenser (Shell & Tube)
In this part, two pass shell and tube heat exchanger was designed by using the same conditions with first counter flow type heat exchanger for condenser. The process was divided into two parts; cooling and phase change part. They were thought like two different heat exchangers. For the cooling part, U was assumed initially as
U=0.44 kW/(m2K), which was calculated previously at simple desgn of counter flow type hex. Then, UA was found by using ε-NTU method. After that, area and initial length was calculated. Using the initial length, and the formulas which can be found at the following used to calculate htube (hi) and hshell (ho) values. 0.5 ∗ ∗ ∗
2⁄
3

(1.07 + 12.7 ∗ √(0.5 ∗ ) ∗ (()
ℎ =

− 1))



With these values, new U was calculated and new UA is also availible. Using an iterative process; number of tubes, length and pressure drops were calculated. Restictions were obeyed during this iterative process. The inputs and outputs are the followings;
Tube diameter: 29mm ϕ=1(assumed, which was used at calculation of pressure drop of shell side)
Number of tubes: 20
Length:2.87meters
Shell diameter:190mm
Pressure drop for shell side: 673kPa
Pressure drop for tube side:231kPa

=

∗ ∗ 2 ∗ 2 = 0.637 ∗ (
)
∗ = 0.4 ∗ = 4 ∗ ( 2 − ∗

2
1
)∗
4


= ∗ ( − ) ∗ =
ℎ =

∗ ∗

0.36 ∗ ∗ 0.55 ∗ 0.33

4 ∗ = ∗ 2 ∗ ∗

For phase change part, the procedure is nearly same. U was assumed initially as U=0.90
Kw/(m2*K). For htube (hi) value, nusselt number correlation for phase change was used which is availible in counterflow hex simple design part. For the tube side during phase change, averages of each variables were taken
(average value of liquid viscosity and gas viscosity for example) as an assumption. The inputs and outputs are the followings.
Tube diameter: 60mm ϕ=1(assumed, which was used at calculation of pressure drop of shell side)
Number of tubes: 86
Length:9.67meters
Shell diameter:830mm
Pressure drop for shell side: 0.03kPa
Pressure drop for tube side:1.3Mpa

The following formulas was used to calculate pressure drop formulas for shell side and tube side. 

= exp(0.576 − 0.19 ∗ ln())




= ⁄



=

−1

∗ 2 ∗ ( + 1) ∗
∆ =
2 ∗ ∗ ∗ ∅
∆ = (

4 ∗ ∗ ∗ ∗ 2
+ 4 ∗ ) ∗

2

To conclude, length seems to be reasonable for each heat exchanger. However, pressure drops are very high for shell side. Also, the detailed calculations can be provided if required in which all the matlab codes are availible for
“counterflow hex simple design for condenser”,
“Rating of counterflow hex for condenser” and
“simple design of shell and tube hex for condenser”. For this project, the desired work output for group E is between 50 and 100 kW. The work output for the simple design with 800kPa was calculated as 67 kPa and 58 kPa for the 650kPa evaporator which is in the desired range of the
ORC.

5. RATING
This part of the assignment requires changing the mass flow rates of all the fluids by 20 %.
The results found were graphed to show the trend of how changing the mass flow rate affects outlet temperatures and the work output of the overall Organic Rankine Cycle.
In the rating part area was kept constant which was taken from simple design. The approach roughly was as follows for each mass flow rate
(which may change slightly for evaporator or condenser): 


Determine overall heat transfer coefficient as to obtain the UA value
Calculate NTU=UA/Cmin
Calculate the effectiveness ɛ(C*, NTU) using the tables
Since Cc and Ch are known Qmax can be determined using the inlet and exit temperatures Q= ε*Qmax may then be found
Finally outlet temperatres can be determined (for the condenser inlet temperature of refrigerant is calculated whereas outlet is kept constant, see part
4. for details.)

5.1 Evaporator at 800 kPa (Counter
Flow)
It is observed that increasing the mass flow rate of the refrigerant decreases both the outlet temperatures (water(hot) and refrigerant(cold)) but has an obvious effect on the outlet temperature of the geothermal source (i.e. the outer and hotter fluid) whereas not a noticeable effect on the outlet temperature of the R245fa refrigerant (Fig 1). This is what was expected from the results. This further shows that increasing mass flow rate on the refrigerant side will reduce the overall heat transfer between the two fluids.
On the other hand increasing the water mass flow rate would increase the outlet temperature of the refrigerant and decrease it for the water but only a minor change is observed (Fig 2). It can also be seen that the increase and decrease in outlet temperatures of the refrigerant and the water respectively starts decreasing, and eventually a mass flow rate will be achieved where a further increase in mass flow rate will not affect the temperature outlet. This implies that increasing mass flow rate on the water side will increase the overall heat transfer between the two fluids to a certain value after which it will remain constant.

900.00
92

850.00

88

Qtot,in (kW)

Temperature (celcius)

90
86
84
82

800.00
750.00
700.00

80
650.00

78
76

600.00

74

3.00
3.00

3.40

3.80

4.20

4.60

5.00

5.40

3.40

3.80

4.20

4.60

5.00

5.40

Mass flowrate of ref (kg/s)

mass flowrate of ref (kg/s)

mref vs Qtot,in mref vs Tho

mref vs Tco
Figure 4

Figure 2

860.00
94
840.00

93

820.00

Qtot,in (KW)

Temperatures(celcius)

93.5
92.5
92
91.5
91

800.00
780.00
760.00

90.5

740.00

90

720.00

89.5
7

8

9

10

11

12

mass flowrate of water mwat vs Tho

mwat vs Tco

Figure 3

The heat input of the cycle increases with increase in the mass flow rate of the refrigerant
(Fig 3) and also with the mass flow rate of the water (Fig 4).

13

7.5

8.5

9.5

10.5

11.5

12.5

mass flowrate of water(kg/s) mwat vs Qtot,in
Figure 5

When the refrigerant side mass flow rate is increased the total pressure losses increase (Fig
5) as it obvious from the formula used for pressure loss. It depends on the square of the mass flow rate and hence increases the pressure losses. increase in mass flow rate will not affect the temperature outlet. This implies that increasing mass flow rate on the water side will increase the overall heat transfer between the two fluids to a certain value after which it will remain constant. 5.00
4.60
3.80
3.40
3.00
2.60
2.20
1.80
1.40
1.00
3.00

3.40

3.80

4.20

4.60

5.00

mass flowrate (kg/s) mref vs Pressure loss

5.40

Temperature (celcius)

Pressure loss (KPa)

4.20

90.00
85.00
80.00
75.00
70.00
65.00
60.00
55.00
50.00
3.00 3.40 3.80 4.20 4.60 5.00 5.40

Figure 6

mass flowrate (kg/s)

The work output graphs are shown and discussed in the conclusion (Fig 19 & 20).All the calculations done using EXCEL 2013 for the evaporator can be made available if required.

mref vs Tho
Figure 7

5.2Evaporator at 650 kPa (Counter Flow)

On the other hand increasing the water mass flow rate would increase both of the outlet temperature of the refrigerant and the water but only a minor change is observed for the refrigerant outlet temperature (Fig 8). It can also be seen that the increase and decrease in outlet temperatures of the refrigerant and the water respectively starts decreasing, and eventually a mass flow rate will be achieved where a further

86

Temperatures(celcius)

It is observed that increasing the mass flow rate of the refrigerant decreases both the outlet temperatures (water(hot) and refrigerant(cold)) but has an obvious effect on the outlet temperature of the geothermal source (i.e. the outer and hotter fluid) whereas not a noticeable effect on the outlet temperature of the R245fa refrigerant (Fig 7). This is what was expected from the results. This further shows that increasing mass flow rate on the refrigerant side will reduce the overall heat transfer between the two fluids.

mref vs Tco

85.5
85
84.5
84
83.5
83
7

9

11

13

mass flowrate of water mwat vs Tho

mwat vs Tco

Figure 8

The heat input of the cycle increases with increase in the mass flow rate of the refrigerant
(Fig 9) and also with the mass flow rate of the water (Fig 10).

900.00

Pressure loss (KPa)

Qtot,in (KW)

850.00
800.00
750.00
700.00

650.00
600.00
3.00

3.40

3.80

4.20

4.60

5.00

5.40

9.80
9.00
8.20
7.40
6.60
5.80
5.00
4.20
3.40
2.60
1.80
1.00
3.00

Mass flowrate (kg/s)

3.80

4.20

4.60

5.00

5.40

mass flowrate (kg/s)

mref vs Qtot,in

mref vs Pressure loss

Figure 9

Figure 11

The work output of the cycle decreases when the mass flow rate of the refrigerant is increased (Fig 12) whereas the vice versa is observed when outer fluid’s mass flow rate is increased (Fig 13). The work output with this evaporator is obviously lower than the work output with evaporator at 800 kPa (Fig 19 &
20). For this reason the efficiency of the cycle is also lower, 7.33 %, compared to the other one
(see conclusion).

840
820

Qtot,in (KW)

3.40

800
780
760
740
720
700
7.5

8.5

9.5

10.5

11.5

12.5

120.00

mass flowrate of water(kg/s)

100.00

Figure 10

When the refrigerant side mass flow rate is increased the total pressure losses increase (Fig
11) as it obvious from the formula used for pressure loss. It depends on the square of the mass flow rate and hence increases the pressure losses. Woutput [kW]

mwat vs Qtot,in

80.00
60.00
40.00
20.00
0.00
3.00

3.50

4.00

4.50

mref [kg/s]
Figure 12

5.00

5.50

60

-30

-20

-10

50
40

Temp [C]

Woutput [kW

100
90
80
70
60
50
40
30
20
10
0

30
20
10

0

10

20

30

change in mouterfluid [%]

0
3.00

3.50

4.00

change in % of mouter fluid

4.50

5.00

5.50

mref [kg/s] mref vs Trefin

Figure 13

All the calculations done using EXCEL 2013 for the evaporator can be made available if required.

5.3. Condenser (Counter Flow)
Changing the mass flow rate of the refrigerant on the condenser increases the inlet temperature and decreases the outlet temperature of the coolant (water) if the outer refrigerant temperature is kept constant (Fig 14). This was done to avoid the outlet refrigerant temperature to reach the subcooled region in order to simplify the calculations. On the other side the temperature outlet of the coolant will decrease when mass flow rate of water is increased (Fig
15). This also corresponds to a lower heat transfer. mref vs Tcoolant,o

Figure 15

The increase in mass flow rate of the refrigerant almost gives a linear increase in the Qout from the condenser (Fig 16). This is obvious since increase in this mass flow rate has a proportional effect on the heat transfer rate. The increase in the coolant mass flow rate also corresponds to a higher Qout of the system but at a decreasing rate (Fig 17). A value will be reached when
Qout does not increase with further increase in mass flow rate of water.
900.0
850.0
800.0

Qout [kW]

Temp [C]

50
40
30
20

750.0
700.0
650.0
600.0

10
12.00

550.0
14.00

16.00

18.00

20.00

mwater [kg/s] mwater vs Tref,i

mwater vs Tcoolant,o

500.0
3.00

3.50

4.00

4.50

mref [kg/s] mref vs Qout

Figure 14
Figure 16

5.00

5.50

5.4. Conclusion

750.0

Qout [kW]

740.0
730.0

720.0
710.0
700.0
690.0
12.00

14.00

16.00

18.00

20.00

mwater [kg/s]

For this project, the desired work output for group E is between 50 and 100 kW. The work output for the simple design was calculated as
67.21 kPa which is in the desired range of the
ORC. The efficiency of the cycle is calculated as
8.53 % which is acceptable as it should be close to 10 % for an ORC [1]. It can be seen that the work output decreases with increasing the mass flow rate of the refrigerant in the ORC. It can be observed from that by decreasing the mass flow rate of refrigerant up to 20%, optimum work output can be achieved.
120.00

mwater vs Qout

100.00

Woutput [kW]

Figure 17

When the refrigerant side mass flow rate is increased the total pressure losses increase (Fig
18) as it obvious from the formula used for pressure loss. It depends on the square of the mass flow rate and hence increases the pressure losses. 80.00
60.00
40.00
20.00
0.00
3.00

3.50

6

4.00

4.50

5.00

5.50

20

30

mref [kg/s]

5.5
Figure 19

4.5
120.00

4
3.5

100.00

Woutput [kW

dPloss [kPa]

5

3
2.5
2
3.00

3.50

4.00

4.50

5.00

80.00
60.00
40.00
20.00

5.50

mref [kg/s] mref vs total dPloss

0.00
-30

-20

-10

0

10

change in mouterfluid [%] change in % of mouter fluid

Figure 18

All the calculations done using MATLAB
R2013a for the condenser will be available in the Appendix of the Final report prepared for this project.

Figure 20

6.

REFERENCES
1. Lee D. H. (et al.), “Development and
Test of a 100 kW Class ORC PowerGenerator for Low Temperature
Geothermal Applications”, 2015.
2. Infinityturbine.com, ‘IT50 ORC Infinity
Turbine', 2015. [Online]. Available: http://www.infinityturbine.com/. [Accessed: Oct-2015].
3. Brasz L. J. , Bilbow W. M., “Ranking of
Working Fluids for Organic Rankine
Cycle Applications”, 2004.
4. Wang E.H. (et al.), “Study of working fluid selection of organic Rankine cycle
(ORC) for engine waste heat recovery”,2011. 5. Instituteforenergyresearch.org,
“Electricity Distribution”,1998. http://instituteforenergyresearch.org/elec tricity-distribution/. [Accessed: Oct2015].
6. S. Kakac and H. Liu, “Heat Exchangers:
Selection, Rating and Thermal Design”,
2002.
7. I. Frank, (et al.), “Principles of Heat and
Mass transfer”, 2013
8. S. Ramesh and S. Dusan,
“Fundamentals of Heat Echanger
Design”, 2003.
9. Y. Almila,”ME 421 Heat Exchanger
Design”, 2014

Similar Documents

Free Essay

Mea Heat Exchanger Design

...lean/rich MEA heat exchanger E-114. This heat exchanger is a counter flow shell and tube heat exchanger and is designed to heat up the rich MEA stream flowing from the CO2 absorber to the stripper. The principle that is applied is heat exchange between cold stream and hot stream which in this case the heat energy is transferred from the lean MEA stream to the rich MEA stream. Apart from this, the chemical engineering design for this heat exchanger includes the determination of its dimensions and heat exchange coefficient as well as pressure drop. The mechanical design covers the design of pressure vessel, head, supports and piping. In addition, the operating design which includes the commissioning, start-up, shutdown and maintenance procedures, process control, and HAZOP study is considered. 2.0 Process Description Figure 2.1 Schematic of rich/lean MEA heat exchange process flow sheet The lean/rich MEA heat exchange process is presented in Figure 2.1. The MEA-2 stream containing rich CO2 is flowing from CO2 absorber and enters the heat exchanger to be heated up from 61°C to 80°C by MEA-7 before entering the stripper. The MEA-7 is then cooled down from 105°C to 84°C when pass through the heat exchanger and recycle back to the CO2 absorber. The cold stream in this case is MEA-2 and MEA-3 while the hot stream is MEA-7 and MEA-8. 3.0 Chemical Engineering Design 3.1 Design Methodology The rich/lean MEA heat exchanger is a counter flow shell and tube heat exchanger. The chemical...

Words: 3516 - Pages: 15

Free Essay

Heat Pump

...trODuct ION tO G rO u N D S O u rc e Heat P uMP SyS teM S chris arkins This note TEC 6, originally published in February 1999, was reviewed by Chris Arkins in January 2004. This summary page includes recent updates to the topic since publication. SUMMARY OF actIONS tOwarDS SuStaINable OutcOMeS Introduction Alternative low energy air conditioning solutions are now commonly sought in preference to typical air conditioning systems for both residential and commercial applications. The industry has seen a growing emergence of ground source heat pump (GSHP) installations throughout Australia over the last five years. A broad spectrum of facilities ranging from domestic housing, hospitals, education facilities, commercial offices and civic buildings to name a few, are now realising the environmental benefits offered by GSHP systems over more commonly used air conditioning systems. This summary note provides a brief overview of the previous note and provides an update on changes that have occurred since. basic Strategies Heat rejection is fundamental to all air conditioning systems. Typically, unsightly roof mounted air cooled condensers and cooling towers are by far the most commonly used method for rejecting heat from a building. Ground source heat pumps are somewhat different to the norm. Basically GSHP are refrigeration machines that provide heating and cooling by using ground water and the earth as a medium to reject and/or absorb heat and as such do not require air cooled...

Words: 3545 - Pages: 15

Free Essay

Design of a Finned Radiator Assembly

...441 | Design of a Finned Radiator Assembly | Heat Exchanger Design Project | Thien Van TranChris LongfieldEric PacewiczOlivia Ching | | 4/3/2012 | | Scope of the Project The objective of the project was to design an effective radiator assembly to accommodate the Diesel-Engine Generator Set 1500-XC6DT2 by incorporating the use of tubes with inner fins in various geometries in order to meet the heat rejection requirements specified. This was done with consideration for minimizing cost, size, and complexity. Initial Parameters The initial parameters were the operating requirements of the Diesel-Engine Generator Set 1500-XC6DT2 are as follows: * Coolant capacity – The coolant chosen for our radiator is ethylene glycol (50/50 % by volume) * Its maximum operating temperature of 225F * Air flow rate – Since the generator is stationary as opposed to that used in an automobile application, a fan will be needed to provide the necessary flow rate. The required air flow rate specified by the engine is 9.383 m3/s in order to dissipate the heat generated * Coolant flow rate – The coolant flow rate is 17.914 kg/s through the radiator * The initial coolant temperature is assumed to be 212F, which is slightly below the operating temperature of the engine. The initial coolant temperature is taken as the ethylene glycol entering the radiator immediately after leaving the engine. * Pressure drop allowance – The * The total heat rejected...

Words: 1400 - Pages: 6

Premium Essay

Pressurized Water Reactor Steam Generator Material Problems Solutions to Prevent Capacity Loss and Extend Lifetime

...the steam generator, with both consequences resulting in a loss of profit to the operating utility. Specific problems associated with steam generator materials that are discussed include denting, stress corrosion cracking (SCC), phosphate thinning, as well as vibration and mechanical problems. A connection is established between material issues that affect steam generators and capacity losses as well as decreased lifetime. Finally, solutions are discussed to prevent decreases in capacity and diminished lifetime. Introduction Steam generators are a critical component of PWR. The function of a steam generator in a PWR is to serve as a heat exchanger between the primary and secondary. The heat exchange that occurs between the primary and secondary creates steam, the steam turns a turbine, the process of which generates electricity. The generation of electricity for profit is the purpose of nuclear power plants, therefore material problems associated with steam generators that reduce the capacity of a nuclear power plant to generate electricity are an important profit consideration. Another significant cost and profit consideration is steam generator replacement cost and replacement power costs during the outage. The solving of steam generator tube-related material problems and the maximization of...

Words: 1771 - Pages: 8

Free Essay

Classification of Heat Exchangers

...Classification Of Heat Exchangers Introduction Heat: is energy in transit from one mass to another because of a temperature difference between the two. A form of energy associated with the motion of atoms or molecules and transferred from a body at a higher temperature to one at a lower temperature. Heat energy will move from a high energy state to that of a lower energy state. The process will continue until a state of equilibrium is reached. Equilibrium is the energy state where the material is at the same energy level as its surroundings. A heat exchanger is defined as device used to transfer thermal energy (enthalpy) between two or more fluids, between the solid surface and a fluid. The fluids can be single compounds or mixtures. The typical applications of heat exchangers include cooling or heating of fluid stream of concern, evaporation or condensation of multi-component or single fluid stream. They are also used in heat rejection or heat recovery from a system. The heat exchanger: Is a piece of equipment built for efficient heat transfer from one medium to another? The media may be separated by a solid wall, so that they never mix, or they may be in direct contact. Heat exchangers are found in most chemical or mechanical systems. They serve as the system's means of gaining or rejecting heat. Some of the more common applications are found in heating, ventilation and air conditioning (HVAC) systems, radiators on internal combustion engines, boilers, condensers,...

Words: 828 - Pages: 4

Free Essay

Heat Exchangers

...the secondary fluid to the heat exchanger may change with time. This means that in order to maintain a consistent secondary fluid outlet temperature, the heat supplied to the heat exchanger must also vary. This can be achieved by using a control valve on the inlet to the primary side of the heat exchanger, as shown in Figure 13.2.1. Fig. 13.2.1 Typical temperature control of a steam/water shell and tube heat exchanger A control valve is used to vary the flowrate and pressure of the steam so that the heat input to the heat exchanger can be controlled. Modulating the position of the control valve then controls the outlet temperature of the secondary fluid. A sensor on the secondary fluid outlet monitors its temperature, and provides a signal for the controller. The controller compares the actual temperature with the set temperature and, as a result, signals the actuator to adjust the position of the control valve. For a constant heating area and heat transfer coefficient, the rate at which heat is transferred from the steam to the secondary fluid for a particular heat exchanger is determined by the mean temperature difference between the two fluids. A larger difference in mean temperatures will create a large heat transfer rate and vice versa. On partially closing the control valve, the steam pressure and the temperature difference fall. Conversely, if the control valve is opened so that the steam mass flow and hence pressure in the heat exchanger rise, the mean temperature...

Words: 4745 - Pages: 19

Free Essay

Process Technology

...Voss PCT 105 Equipment April 5, 2012 Heat Exchangers There are many types of heat exchangers used in a wide variety of industrial applications including power plants, boilers for industrial steam, chemical plants, and many types of manufacturing facilities. Several different configurations are used to accomplish the function of transferring heat from one fluid to another without mixing the two fluids together. The two most common industrial heat exchangers, the shell and tube heat exchanger and the double pipe heat exchanger, along with information about spiral heat exchangers, flat plate heat exchangers, flat plate heat exchangers, fin-tube heat exchangers, and condensers. Calculations for heat exchanger design use heat transfer parameters such as convection heat transfer coefficients, overall heat transfer coefficients, and log mean temperature differences. These calculations are needed for shell and tube and double pipe heat exchangers, as well as other types. The flow pattern through a heat exchanger affects the required heat exchanger surface. A counter flow heat exchanger needs the lowest heat transfer surface area. It gives a higher value for log mean temperature difference than either a parallel flow heat exchanger or a cross flow heat exchanger. A heat exchanger can have several different flow patterns. Counter flow, parallel flow, and crosss flow are common heat exchanger types. A counter flow heat exchanger is the most efficient flow pattern of...

Words: 1476 - Pages: 6

Free Essay

Feed-Forward Control Applied to Thermally Activated Building Systems

...ZECCHIN Dott. Ing. Michele DE CARLI Dott. Ing. Dietrich SCHMIDT Laureando: Alessio PULLIERO Anno accademico 2003-2004 To my parents …. ABSTRACT The main purpose of this thesis is to investigate different control strategies for the heating and cooling system of the ZUB (Centre for Sustainable Building), situated in Kassel, Germany. It is an experimental office building, with a very detailed monitoring system for studying low-energy and low-exergy building technologies. The conditioning system is a TABS (Thermally Activated Building System), with water pipes embedded in the centre of a structural concrete slab, thus resulting in a ceiling radiant system. The high thermal capacity of the slab offers great opportunities to store heat, to dampen temperature fluctuations or to shift the peak-load; but, on the other hand, it implies a slow response of the system, which requires an accurate regulation strategy to front the variability of several factors, and to achieve the desired indoor temperature. A TRNSYS model of an office room has been developed, thus allowing to implement several regulations in the software and to test their performance. The main conclusion, carried out from the simulations, is that the implementation of a Feed-forward controller gives appreciable advantages in the temperature control, achieving both a more precise control of thermal conditions and a reduction of the energy consumption. The parameters taken into account by the controller are more than...

Words: 22312 - Pages: 90

Premium Essay

Optimization of Heat Exchanger Network

...journal homepage: www.elsevier.com/locate/apthermeng Optimization of heat exchanger network Mofid Gorji-Bandpy, Hossein Yahyazadeh-Jelodar, Mohammadtaghi Khalili* Noshirvani University of Technology, P.O. Box 484, Babol, Iran a r t i c l e i n f o Article history: Received 6 September 2010 Accepted 26 October 2010 Available online 2 November 2010 Keywords: Heat exchanger network (HEN) Optimization Genetic algorithm Pinch Analysis Method Mathematical Optimization Method Sequential Quadratic Programming (SQP) a b s t r a c t In this paper, a new method is presented for optimization of heat exchanger networks making use of genetic algorithm and Sequential Quadratic Programming. The optimization problem is solved in the following two levels: 1- Structure of the optimized network is distinguished through genetic algorithm, and 2- The optimized thermal load of exchangers is determined through Sequential Quadratic Programming. Genetic algorithm uses these values for the determination of the fitness. For assuring the authenticity of the newly presented method, two standard heat exchanger networks are solved numerically. For representing the efficiency and applicability of this method for the industrial issues, an actual industrial optimization problem i.e. Aromatic Unit of Bandar Imam Petrochemistry in Iran is verified. The results indicate that the proposed multistage optimization algorithm of heat exchanger networks is better in all cases than those obtained using traditional...

Words: 4334 - Pages: 18

Free Essay

Chemical Engineering Shell and Tube Heat Transfer

...Horizontal Shell and Tube Heat Exchanger Table of Contents: Nomenclature. Pg. 3 Introduction and Background Pg. 4 Experimental Methodology Equipment and Apparatus Pg. 6 Experimental Procedures Pg. 7 Results Pg. 8 Analysis and Discussion……………………………………………………………………..Pg. 11 Summary and Conclusions Pg. 12 References Pg. 13 Appendices Pg. 14 Nomenclature Symbol | Term | Units | A | Heat transfer surface area for the tubes | Inches2 (in2) | Cp | Heat Capacity | J/(mol*K) | F | Correction Factor | __ | | Heat | W | c | Cold Side Heat Duty | W | H | Hot Side Heat Duty | W | Shell Side | Hot Side | __ | T | Temperature | Celsius | ∆T | Change in Temperature | Celsius | Tube Side | Cold Side | __ | ∆Tlm | Log mean temperature difference | Kelvin (K) | U | Heat Transfer Coefficient | W/(K*in2) | V | Volume | L | ṁH | Hot water flow rate | L/min | ṁC | Cold water flow rate | L/min | 1.0 Introduction and Background A heat exchanger is a device designed to efficiently transfer thermal energy from one fluid to another fluid, which can be a liquid or a gas [1]. These fluids do not mix or come into direct contact with each other. Even though all heat exchangers do the same job of passing heat from fluid to fluid, there are various types that work in many different ways. The two most common types of heat exchangers are the shell-and-tube...

Words: 2748 - Pages: 11

Free Essay

Heat Exchanger Lab

...School of Mechanical and Design Engineering   Dublin Institute of Technology Bachelor of Engineering Technology in Mechanical Engineering   Laboratory 2 Plate Heat Exchanger Assignment Robert O’Donovan Student Number: C12756051 Due Date: 24/10/2014 Lecturer: Jim Ffrench Dublin Institute of technology Bolton Street, Dublin 1. I.  Abstract   Heat exchangers are a piece of process equipment used for heat transfer between two media. The media do not come into direct contact and there is no mixing. Heat is transported from the hot medium to the cold medium by way of a heat conducting partition. In this experiment, we analysed the working principle of parallel and counter flow. We observed different fluid temperatures, fluid flow rates and how this affected the heat exchangers performance. Calculations were needed to determine the variation of the two configurations. There are some possible percentage errors that need to be considered in the experiment, these include the tube changeover from parallel to counter flow, the fluid loss will have an effect on the readings. Also if the unit is not allowed enough time to stabilise when changing the flow rates, the readings will not be accurate. 1"Vh"(L/min) Parallell"flow Counter"flow Vs U"= U"= 3"Vc"(L/min) 2.9"W/m 2 K 3.5"W/m 2 K The percentage difference between the U values is 20.6 %.   II.    Table  of  Contents     1.   INTRODUCTION  ...............

Words: 2209 - Pages: 9

Premium Essay

Geothermal Piles Literature Review

...Literature Review: Geothermal Piles Contents Introduction 3 Background of Geothermal Piles 4 Description of System 4 Construction and Design 4 Construction Process 4 Design Process 5 Design Issues and Deficiencies 5 Uses and Benefits 5 Feasibility and Testing 5 Carbon Accounting 5 Conclusion 5 References 5 Introduction It has become globally recognised that CO₂ emissions need to be massively reduced, if we are to extend the habitable condition of this planet for future generations. In this vein over the past twenty years there have been massive strides in the development of renewable energy technologies. Geothermal Energy is one of the most promising methods of renewable energy generation in the struggle to find a sufficient replacement for fossil fuels. Geothermal Energy or Ground Thermal Energy can be harnessed in a number of ways, including ground source heat pumping systems integrated into boreholes and wells (Boennec, 2008). Energy Foundations or Thermo-active Ground structures is a broad term encompassing almost all subsurface engineering structure, such as bored or prefabricated piles, retaining walls, base slabs and diaphragm walls (Hemmingway & Long, 2013) for example, that have integrated closed loop ground source heat pumping systems to provide heating capacity in winter time and cooling capacity in summer time for almost any purpose building. However, the focus of this paper is on a particular method of Geothermal Energy extraction...

Words: 1465 - Pages: 6

Free Essay

Thermal Design

...understand and design thermal Fluid systems.. The topics will includes review of thermodynamics and heat transfer, Heat Exchanger design, Convective and Conductive heat transfer rate calculations, Discussions of all types of heat exchangers, such as Double pipe, Shell and Tube, and Compact heat exchangers. Also Design of cooling towers, Solar collectors, … will be discussed. Perquisites: Thermodynamics, Dynamic, and Heat Transfer. Textbook: Heat Exchangers, Selection and rating by Sadik Kakac, and Hontan Lee, 3rd edition Reference Books: Hand book of heat exchanger design, Solar Energy Conversions Topics Covered:   |Lecture |Topic | |(Hrs, approx.) | | |5 |Review of heat transfer and thermodynamics | |6 |Classification of Heat exchangers | |3 |Basic Design Methods – Logarithmic mean temperature | |3 |F chart Methods and NTU methods | |6 |Force Convection And Single phase heat exchangers ...

Words: 1552 - Pages: 7

Free Essay

Quiz 1 Egee 101

... | | |C. | | |Natural Gas | | | | | |D. | | |Coal | | | | Correct! [pic] Natural Gas supplies 53% of the fuel used to heat homes during the winter. Natural gas is typically cheaper than other fuels, required no storage, and fairly clean (no ash produced). |[pic]|Points Earned:...

Words: 3715 - Pages: 15

Free Essay

Spartan Heat Exchangers Inc.

...SPARTAN HEAT EXCHANGERS INC. On June 10, Rick Coyne, materials manager at Spartan Heat Exchangers Inc. (Spartan), in Springfield, Missouri, received a call from Max Brisco, vice president of manufacturing: “What can materials department do to facilitate Spartan’s new business strategy? I’ll need your plan in next week.” SPARTAN HEAT EXCHANGERS Spartan was a leading designer and manufacturer of specialized industrial heat transfer equipment. Its customers operated in a number of industries such as steel, aluminium smelting, hydroelectricity generation, pulp and paper, refining, and petrochemical. The company’s primary products included transformer coolers, motor and generator coolers, air-cooled heat exchangers, and transformer oil coolers. Spartan’s combination of fin-tube and time-proven heat exchanger designs had gained wide recognition bot in North America and internationally. Sales revenues were $25 million and Spartan operated in a 125,000-square-foot plant. Spartan was owned by Krimmer Industries, a large privately held corporation with more than 10,000 employees worldwide, head-quartered in Denver. Rick Coyne summarized the business strategy of Spartan during the past ten years: “We were willing to do anything for every customer with respect to their heat transfer requirements. We were willing to do trial and error on the shop floor and provide a customer with his or her own unique heat transfer products.” He added, “Our design and manufacturing people derived greatest...

Words: 1117 - Pages: 5