Temperature controlled applications
In a temperature control application, the inlet temperature of the secondary fluid to the heat exchanger may change with time. This means that in order to maintain a consistent secondary fluid outlet temperature, the heat supplied to the heat exchanger must also vary. This can be achieved by using a control valve on the inlet to the primary side of the heat exchanger, as shown in Figure 13.2.1.
Fig. 13.2.1 Typical temperature control of a steam/water shell and tube heat exchanger
A control valve is used to vary the flowrate and pressure of the steam so that the heat input to the heat exchanger can be controlled. Modulating the position of the control valve then controls the outlet temperature of the secondary fluid. A sensor on the secondary fluid outlet monitors its temperature, and provides a signal for the controller. The controller compares the actual temperature with the set temperature and, as a result, signals the actuator to adjust the position of the control valve.

For a constant heating area and heat transfer coefficient, the rate at which heat is transferred from the steam to the secondary fluid for a particular heat exchanger is determined by the mean temperature difference between the two fluids. A larger difference in mean temperatures will create a large heat transfer rate and vice versa. On partially closing the control valve, the steam pressure and the temperature difference fall. Conversely, if the control valve is opened so that the steam mass flow and hence pressure in the heat exchanger rise, the mean temperature difference between the two fluids increases.

Altering the steam pressure will also slightly affect the amount of heat energy available in the condensing steam as the enthalpy of evaporation actually falls with increasing pressure. This means that the latent heat available per kg of steam reduces as the steam pressure increases. If steam flow accuracy is required, this must be accounted for.
Example 13.2.1
A manufacturer is to design a heat exchanger in which the specification calls for steam at 4 bar g to heat secondary water from 10°C to 60°C. The water flow is to be constant at all loads at 1.5 L/s.
It is assumed that 1 litre of water has a mass of 1 kg, so the mass flowrate = 1.5 L/s x 1 kg/L = 1.5 kg/s.
The manufacturer uses a heat transfer coefficient 'U' for the heat exchanger of 2500 W/m2°C.
Take the specific heat of water as 4.19 kJ/kg°C.
Determine:
(A) The design heat load.

(B) The corresponding steam flowrate.

(C) The minimum heating area required.

Also, if the customer's minimum heat load occurs when the inlet water temperature rises to 30°C, determine:

(D) The minimum heat load.

(E) The corresponding steam pressure in the heat exchanger.

(F) The corresponding steam flowrate.
Calculations
(A) Find the design heat load using the heat transfer flowrate equation (Equation 2.6.5):
Equation 2.6.5
Where:
| = | Mean heat transfer rate (kW) | | = | Mean secondary fluid flowrate (kg) | cp | = | Specific heat capacity of the secondary fluid (kJ/kg K) or (kJ/kg°C) | ΔT | = | Temperature rise of the secondary fluid (K or °C) |

(B) Find the corresponding steam flowrate at 4 bar g, saturation temperature (T s) is 152°C, and hfg = 2108.1 kJ/kg (from steam tables). Calculate the required steam flow at the design condition using Equation 2.8.1:
Equation 2.8.1

(C) Find the minimum heating area to meet the requirement using Equation 2.5.5. Note; the manufacturer uses the Logarithmic Mean Temperature Difference (ΔT LM) to calculate the minimum amount of heating area to satisfy the design rating:
Equation 2.5.5
Where
: ΔT LM | = Logarithmic Mean Temperature Difference (LMTD) | T s | = Steam temperature (°C) | T 1 | = Secondary fluid in temperature (°C) | T 2 | = Secondary fluid out temperature (°C) | ln | = The mathematical function known as 'natural logarithm' |

By re-arranging the general heat transfer equation (Equation 2.5.3: = U x A x ΔT) Equation 13.2.1 can be formulated, where ΔT can be represented by the mean value ΔT M.
Equation 13.2.1
Where
: A | = Heating area (m²) | | = Mean heat transfer rate (W) | U | = Heat transfer coefficient (W/m²°C) | ΔT M | = Mean Temperature Difference. Note: ΔT M may be either ΔT LM (LMTD) or ΔT AM (AMTD). |

For the purpose of this example it will be assumed that the heat exchanger is designed to have exactly this area of 1.09 m².

(D) Find the minimum heat load, when the inlet water temperature is 30°C, using the heat transfer flowrate equation (Equation 2.6.5) as used in Part 'A' of these calculations:
Equation 2.6.5

To calculate the corresponding steam flowrate, it is first necessary to determine the steam temperature at the minimum load condition.

It is possible to use the ΔT LM design figures to accurately predict the steam temperature for any load condition, but this requires the use of logarithmic calculations. However, once the exchanger size is fixed and the design temperatures are known, it is much easier to predict operating temperatures using what could be termed a heat exchanger Temperature Design Constant (TDC). The TDC method does not require logarithmic calculations. Please note: TDC cannot be used on those applications where the secondary flowrate varies or where control is achieved by varying the condensate level in the steam space.

Note: When sizing a heat exchanger it is normal for heat exchanger manufacturers to use the ΔT LM method. Once sized, by knowing the heating area and the full-load operating temperatures, TDC can be used to accurately predict all operating temperatures resulting from changes in load, as can be seen in the following text.

Operating temperatures can also be predicted graphically by using what is termed a 'Stall Chart'. This method is discussed in Tutorials 13.5, 13.6, and 13.7.

Temperature Design Constant (TDC)
For any type of steam-heated exchanger with the secondary liquid flowing at a constant rate, TDC can be calculated from the test figures quoted by the manufacturer for full-load. If these data sets are not available and the heat exchanger is already installed in service, TDC can be calculated by observing the steam pressure (and finding the steam temperature from steam tables) and the corresponding secondary inlet and outlet temperatures at any load.

TDC is the ratio of the steam to water temperatures at the inlet and outlet; and is shown in Equation 13.2.2.
Equation 13.2.2
Where
: | TDC | = Temperature Design Constant | T s | = Steam temperature | T 1 | = Secondary fluid inlet temperature | T 2 | = Secondary fluid outlet temperature |
In Example 13.2.1 at full-load conditions:

The TDC equation can be transposed to find any one variable as long as the other three variables are known. The following equations are derived from the TDC equation (Equation 13.2.2).

To find the steam temperature at any load use Equation 13.2.3:
Equation 13.2.3
To find the secondary fluid inlet temperature at any load use Equation 13.2.4:
Equation 13.2.4
To find the secondary fluid outlet temperature at any load use Equation 13.2.5:
Equation 13.2.5
For any heat exchanger with a constant secondary flowrate, the operating steam temperature can be calculated for any combination of inlet temperature and outlet temperature.

In Example 13.2.1 the secondary outlet temperature remains at 60°C, and minimum load occurs when the inlet temperature is 30°C. What is the steam temperature at minimum load?

Inlet temperature = 30°C

Outlet temperature = 60°C

Using Equation 13.2.3:

(E) Find the corresponding heat exchanger steam pressure and enthalpy at minimum load

From steam tables:

A steam temperature of 115.2°C corresponds with a steam pressure of 0.7 bar g.

The specific enthalpy of evaporation at 0.7 bar g (hfg) = 2 215 kJ/kg.

(F) Find the steam flowrate at minimum load:

From (D) the minimum heat load is 188.5 kW.

From (E) the hfg is 2 215 kJ/kg.

Using Equation 2.8.1:
Equation 2.8.1

The term heat exchanger strictly applies to all types of equipment in which heat transfer is promoted from one medium to another. A domestic radiator, where hot water gives up its heat to the ambient air, may be described as a heat exchanger. Similarly, a steam boiler where combustion gases give up their heat to water in order to achieve evaporation, may be described as a fired heat exchanger.

However, the term is often more specifically applied to shell and tube heat exchangers or plate heat exchangers, where a primary fluid such as steam is used to heat a process fluid. A shell and tube heat exchanger used to heat water for space heating (using either steam or water) is often referred to as a non-storage calorifier. (A storage calorifier, as shown in Figure 2.13.1, is constructed differently, it usually consists of a hot water storage vessel with a primary heating coil inside).
Fig. 2.13.1
A storage calorifier installation
Manufacturers often provide a thermal rating for their heat exchangers in kW, and from this the steam consumption may be determined, as for air heater batteries. However, heat exchangers (particularly shell and tube) are frequently too large for the systems which they are required to serve.

A non-storage calorifier (as shown in Figure 2.13.2) will normally be selected from a standard range of sizes, and may often have a much larger capacity than the design figure. For the hot water heating of buildings there may also be certain safety factors included in the heat load calculations.

Plate heat exchangers may also be chosen from a standard range of sizes if the units are brazed or welded. However, there is more flexibility in the sizing of gasketed plate heat exchangers, where plates can often be added or removed to achieve the desired heat transfer area. In many cases, plate heat exchangers are oversized simply to reduce the pressure drop for the secondary fluid.

On existing plant, an indication of actual load may be obtained if the flow and return temperatures and the pumping rate are known. However, it is important to note that throughput as given on the pump maker's plate will probably relate to a pressure head, which may or may not be present in practice.
Fig. 2.13.2
A Non-storage calorifier installation
Steam consumption calculations for heat exchangers
Shell and tube heat exchangers and plate heat exchangers are typical examples of flow type applications. Therefore, when determining the steam consumption for these applications, Equation 2.6.5 should be used.

The start-up load may be ignored if it occurs rarely, or if the time taken to reach full-load output is not too important. Heat exchangers are more often sized on the full running load, with the possible addition of safety factors.

Heat losses are rarely taken into account with these flow type applications, as they are significantly less than the full running load. Shell and tube heat exchangers are usually lagged to prevent heat loss, and to prevent possible injury to personnel. Plate heat exchangers tend to be more compact and have a much smaller surface area exposed to the ambient air, in relation to the size of the unit.
Example 2.13.1
Determine the heat load and steam load of the following non-storage heating calorifier

A heating calorifier is designed to operate at full-load with steam at 2.8 bar g in the primary steam space.

The secondary water flow and return temperatures are 82°C and 71°C respectively, at a pumped water rate of 7.2 kg/s.

cp for water = 4.19 kJ/kg°C
Table 2.13.1
Extract from steam tables
Part 1 - Determine the heat load
The full-load may be calculated using Equation 2.6.5:
Equation 2.6.5
Where:
| = | Quantity of heat energy (kW) kJ/s) | | = | Secondary fluid flowrate = 7.2 kg/s | cp | = | Specific heat capacity of the water = 4.19 kJ/kg°C | ΔT | = | Temperature rise of the substance (82 - 71) = 11°C | | = | 7.2 kg/s × 4.19 kJ/kg°C × 11°C | | = | 332 kW |
Part 2 - Determine the steam load
The full-load condensing rate can be determined using the left hand side of the heat balance Equation 2.6.6:
Equation 2.6.6
Where:
s | = | Steam consumption (kg/s) | hfg | = | Specific enthalpy of evaporation (kJ/kg) | | = | Heat transfer rate (kW) |
Rearranging: a 332 kW calorifier working at 2.8 bar g (hfg = 2 139 kJ/kg from steam tables) will condense:

Plate heat exchangers
A plate heat exchanger consists of a series of thin corrugated metal plates between which a number of channels are formed, with the primary and secondary fluids flowing through alternate channels. Heat transfer takes place from the primary fluid steam to the secondary process fluid in adjacent channels across the plate. Figure 2.13.3 shows a schematic representation of a plate heat exchanger.
Fig. 2.13.3
Schematic diagram of a plate heat exchanger
A corrugated pattern of ridges increases the rigidity of the plates and provides greater support against differential pressures. This pattern also creates turbulent flow in the channels, improving heat transfer efficiency, which tends to make the plate heat exchanger more compact than a traditional shell and tube heat exchanger. The promotion of turbulent flow also eliminates the presence of stagnant areas and thus reduces fouling. The plates will usually be coated on the primary side, in order to promote the dropwise condensation of steam.

The steam heat exchanger market was dominated in the past by the shell and tube heat exchanger, whilst plate heat exchangers have often been favoured in the food processing industry and used water heating. However, recent design advances mean that plate heat exchangers are now equally suited to steam heating applications.

A plate heat exchanger may permit both the condensing and sub-cooling of condensate within a single unit. If the condensate is drained to an atmospheric receiver, by reducing the condensate temperature, the amount of flash steam lost to the atmosphere through the receiver vent is also reduced. This can eliminate the need for a separate sub-cooler or flash steam recovery system.

Although a nominal heat transfer area may theoretically be calculated using Equation 2.5.3, plate heat exchangers are proprietary designs and will normally be specified in consultation with the manufacturers.
Gasketed plate heat exchangers (plate and frame heat exchangers)
In a gasketed plate heat exchanger the plates are clamped together in a frame, and a thin gasket (usually a synthetic polymer) seals each plate around the edge. Tightening bolts fitted between the plates are used to compress the plate pack between the frame plate and the pressure plate. This design allows easy dismantling of the unit for cleaning, and allows the capacity of the unit to be modified by the simple addition or removal of plates.

The use of gaskets gives a degree of flexibility to the plate pack, offering some resistance to thermal fatigue and sudden pressure variations. This makes some types of gasketed plate heat exchanger an ideal choice as a steam heater for instantaneous hot water supply, where the plates will be exposed to a certain amount of thermal cycling.

The limitation in the use of the gasketed plate heat exchanger lies in the operating temperature range of the gaskets, which places a restriction on the steam pressure that may be used on these units.
Brazed plate heat exchangers
In a brazed plate heat exchanger all the plates are brazed together (normally using copper or nickel) in a vacuum furnace. It is a development of the gasketed plate heat exchanger, and was developed to provide more resistance to higher pressures and temperatures at a relatively low cost.

However, unlike the gasketed unit, the brazed plate heat exchanger cannot be dismantled. If cleaning is required it must be either back-flushed or chemically cleaned. It also means that these units come in a standard range of sizes, consequently oversizing is common.

While the brazed heat exchanger has a more robust design than the gasketed type, it is also more prone to thermal fatigue due to its more rigid construction. Any sudden or frequent changes in temperature and load should therefore be avoided, and greater attention should be paid to the control on the steam side to avoid thermal stress.

Brazed heat exchangers are more suitable (and primarily used) for applications where temperature variations are slow, such as in space heating. They may also successfully be used with secondary fluids which expand gradually, such as thermal oil.
Welded plate heat exchangers
In a welded plate heat exchanger the plate pack is held together by welded seams between the plates. The use of laser welding techniques allows the plate pack to be more flexible than a brazed plate pack, enabling the welded unit to be more resistant to pressure pulsation and thermal cycling. The high temperature and pressure operating limits of the welded unit mean that these heat exchangers normally have a higher specification, and are more suited to heavy duty process industry applications. They are often used where a high pressure or temperature performance is required, or when viscous media such as oil and other hydrocarbons are to be heated.
Shell and tube heat exchangers
The shell and tube heat exchanger is probably the most common method of providing indirect heat exchange in industrial process applications. A shell and tube heat exchanger consists of a bundle of tubes enclosed in a cylindrical shell. The ends of the tubes are fitted into tube sheets, which separate the primary and the secondary fluids.

Where condensing steam is used as the heating medium, the heat exchanger is usually horizontal with condensation taking place inside the tubes. Sub-cooling may also be used as a means to recover some extra heat from the condensate in the heat exchanger. However, if the degree of sub-cooling required is relatively large it is often more convenient to use a separate condensate cooler.
Steam heated non-storage calorifiers
A common design for a steam to water non-storage calorifier is shown in Figure 2.13.4. This is known as a 'one shell pass two tube pass' type of shell and tube heat exchanger and consists of a U-tube bundle fitted into a fixed tube sheet.
Fig. 2.13.4
Schematic diagram of a shell and tube heat exchanger
It is said to have 'one shell pass' because the secondary fluid inlet and outlet connections are at different ends of the heat exchanger, consequently the shell side fluid passes the length of the unit only once. It is said to have two tube passes because the steam inlet and outlet connections are at the same end of the exchanger, so that the tube-side fluid passes the length of the unit twice.

A pass partition (also called a partition plate or a feather plate) divides up the exchanger header, so that the tube-side fluid is diverted down the U-tube bundle rather than straight through the header.

This is a comparatively simple and inexpensive design because only one tube sheet is required, but it is limited in use to relatively clean fluids as the tubes are more difficult to clean. Note; it is more difficult to replace a tube with these types of heat exchanger.

Baffles are usually provided in the shell, to direct the shell-side fluid stream across the tubes, improving the rate of heat transfer, and to support the tubes.
Starting from cold
As mentioned in Tutorial 2.7, the start-up load can often be ignored if it seldom occurs or if the time taken to reach full-load output is not critical. For this reason, control valves and heat exchangers will often be found to be sized on full-load plus the usual safety factors.

With systems that shut down at night and weekends, secondary water temperature can be low at start-up on a cold winter morning, and condensing rates in heating calorifiers will be higher than the full-load condition. Consequently, pressure in the steam space may be considerably below the pressure at which the heat exchanger normally operates, until the secondary inlet temperature rises to its design figure.

From a thermal viewpoint, this may not pose a problem - the system simply takes longer to heat up. However, if the designer has not taken this situation into consideration, an inadequate steam trapping and condensate removal system can cause condensate to accumulate in the steam space.

This can cause: * Internal corrosion. * Mechanical stress due to distortion. * Noise, due to waterhammer.
These will cause problems for heat exchangers not designed to withstand such conditions.
Estimating heating loads
Buildings - A practical, subjective method to estimate a heating load is to look at the building itself. Calculations can be complicated, involving factors such as the number of air changes and heat transfer rates through cavity walls, windows and roofs. However, a reasonable estimate can usually be obtained by taking the total building volume and simply allowing 30 - 40 W/m³ of space up to 3 000 m³, and 15 - 30 W/m³ if above 3 000 m³. This will give a reasonable estimate of the heating load when the outside temperature is around a design condition of -1°C.

A practical way to establish steam consumption for an existing installation is to use an accurate reliable steam flowmeter.
Example 2.13.2 Determine the design rating of a heating calorifier from actual measured conditions
The design rating of a heating calorifier is unknown, but the steam load is measured at 227 kg/h when the outside temperature is 7°C and the inside temperature is 19°C, a difference of 12°C.

The calorifier is also designed to provide 19°C inside temperature when the outside temperature is -1°C, a difference of 20°C.

The steam load at the design condition can be estimated simply by the ratio of the temperature differences:

Hot water storage calorifiers
Hot water storage calorifiers are designed to raise the temperature of the entire contents from cold to the storage temperature within a specified period.

The mean rate at which steam is condensed during the heat up or recovery period can be calculated using Equation 2.13.1.
Equation 2.13.1
Where:
s | = | Mean rate of condensation (kg/h) | m | = | Mass of water heated (kg) | cp | = | Specific heat of water (kJ/kg°C) | ΔT | = | Temperature rise (°C) | hfg | = | Enthalpy of evaporation of steam (kJ/kg) | t | = | Recovery time (hours) |
Example 2.13.2 Calculate the mean steam load of a storage calorifier
A storage calorifier has a capacity of 2 272 litres (2 272 kg), and is designed to raise the temperature of this water from 10°C to 60°C in ½ hour with steam at 2 bar g.

cp for water = 4.19 kJ/kg °C
Table 2.13.2
Extract from steam tables
What is the mean rate at which steam is condensed?
Equation 2.13.1
Where:
m | = | 2 272 kg | ΔT | = | 60°C - 10°C = 50°C | hfg | = | 2 163 kJ/kg | t | = | ½ hour |

This mean value can be used to size the control valve. However, when the temperature of water may be at its lowest value, for example 10°C, the high condensing rate of steam may be more than the fully open control valve can pass, and the coil will be starved of steam. The pressure in the coil will drop significantly, with the net effect of reducing the capacity of the steam trapping device. If the trapping device is wrongly sized or selected, condensate may back up into the coil, reducing its ability to transfer heat and achieve the required heat up time. Waterhammer may result, causing severe noise and mechanical stresses to the coil. However, if condensate is not allowed to back up into the coil the system should still maintain the correct heat up time.

The solution is to ensure proper condensate drainage. This could be achieved either by a steam trap or automatic pump-trap depending on the system needs. (Refer to Tutorial 13.1 - Condensate Removal from Heat Exchangers).
Other shell and tube steam heaters
In other heat exchangers using steam an internal floating head may be used, which is generally more versatile than the fixed head of the U-tube exchangers. They are more suitable for use on applications with higher temperature differences between the steam and secondary fluid. As the tube bundle can be removed they can be cleaned more easily. The tube-side fluid is often directed to flow through a number of passes to increase the length of the flow path.

Exchangers are normally built with between one and sixteen tube passes, and the number of passes is selected to achieve the designed tube-side velocity. The tubes are arranged into the number of passes required by dividing up the header using a number of partition plates. Two shell passes are occasionally created by fitting a longitudinal shell-side baffle down the centre of the exchanger, where the temperature difference would be unsuitable for a single pass. Divided flow and split flow arrangements are also used where the pressure drop rather than the heat transfer rate is the controlling factor in the design, to reduce the shell-side pressure drop.

Steam may also be used to evaporate (or vaporise) a liquid, in a type of shell and tube heat exchanger known as a reboiler. These are used in the petroleum industry to vaporise a fraction of the bottom product from a distillation column. These tend to be horizontal, with vaporisation in the shell and condensation in the tubes (see Figure 2.13.5).
Fig. 2.13.5
A kettle reboiler
In forced circulation reboilers the secondary fluid is pumped through the exchanger, whilst in thermosyphon reboilers natural circulation is maintained by differences in density. In kettle reboilers there is no circulation of the secondary fluid, and the tubes are submerged in a pool of liquid.
Table 2.13.3
Typical heat transfer coefficients for some shell and tube heat exchangers
Although it is desirable to achieve dropwise condensation in all these applications, it is often difficult to maintain and is unpredictable. To remain practical, design calculations are generally based on the assumption of filmwise condensation.

The heat transfer area for a shell and tube heat exchanger may be estimated using Equation 2.5.3. Although these units will also normally be specified in consultation with the manufacturers, some typical overall heat transfer coefficients where steam is used as the heating medium (and which include an allowance for fouling) are provided in Table 2.13.3, as a guide.
Corrugated tube heat exchangers
One evolution in the design of the traditional shell and tube heat exchanger, is the recent development of the corrugated tube heat exchanger. This is a single passage fixed plate heat exchanger with a welded shell, and rectilinear corrugated tubes that are suitable for low viscosity fluids. In a similar manner to the plate heat exchangers, the corrugated tubes promote turbulent operating conditions that maximise heat transfer and reduce fouling. Like the traditional shell and tube heat exchangers, these units are commonly installed horizontally. However, in the corrugated tube heat exchanger the steam should always be on the shell side.
Spiral heat exchangers
Spiral heat exchangers share many similar characteristics with shell and tube and plate heat exchangers and are used on many of the same applications. They consist of fabricated metal sheets that are cold worked and welded to form a pair of concentric spiral channels, which are closed by gasketed end-plates bolted to an outer case.

Turbulence in the channels is generally high, with identical flow characteristics being obtained for both fluids. They are also relatively easy to clean and can be used for very heavy fouling fluids and slurries. The use of only a single pass for both fluids, combined with the compactness of the unit, means that pressure drops across the connections are usually quite low.

Fig. 2.13.6
Corrugated tube heat exchangers

Similar Documents

Premium Essay

Spartan Heat Exchangers Inc.

...Group Case Study Spartan Heat Exchangers Inc.   Current State Spartan Heat Exchangers Inc. has been a leading designer and manufacturer of specialized industrial heat transfer equipment for more than 10 years. The company’s primary products are transformer coolers, hydro generator coolers, air-cooled heat exchangers and transformer oil coolers. Their USP are Fin tube type heat exchangers and long lasting products. “… A heat exchanger is a device that is used to transfer thermal energy (enthalpy) between two or more fluids, between a solid surface and a fluid, or between solid particulates and a fluid, at different temperatures and in thermal contact. …” The company is into highly customized heat equipments. Presently, due to entry of new competition from European and Korean companies they have changed their corporate policy, which emphasize on reducing the variety and standardizing the product. The new business policy also aims at reducing the current lead time from 14 weeks to 6 weeks. Problem Statement The Materials Department headed by Rick Coyne has to take many initiatives internally to incorporate the various implications of the new strategy, and submit his report to his boss Max Brisco with the changes suggested by him within a week. The major challenges that Rick faces include: • Change from responsive to anticipatory model of production. • Increase inventory turns from present 4 times to 20 times. • Eliminate material shortages and stock outs. • Reduce...

Words: 2190 - Pages: 9

Free Essay

Classification of Heat Exchangers

...Classification Of Heat Exchangers Introduction Heat: is energy in transit from one mass to another because of a temperature difference between the two. A form of energy associated with the motion of atoms or molecules and transferred from a body at a higher temperature to one at a lower temperature. Heat energy will move from a high energy state to that of a lower energy state. The process will continue until a state of equilibrium is reached. Equilibrium is the energy state where the material is at the same energy level as its surroundings. A heat exchanger is defined as device used to transfer thermal energy (enthalpy) between two or more fluids, between the solid surface and a fluid. The fluids can be single compounds or mixtures. The typical applications of heat exchangers include cooling or heating of fluid stream of concern, evaporation or condensation of multi-component or single fluid stream. They are also used in heat rejection or heat recovery from a system. The heat exchanger: Is a piece of equipment built for efficient heat transfer from one medium to another? The media may be separated by a solid wall, so that they never mix, or they may be in direct contact. Heat exchangers are found in most chemical or mechanical systems. They serve as the system's means of gaining or rejecting heat. Some of the more common applications are found in heating, ventilation and air conditioning (HVAC) systems, radiators on internal combustion engines, boilers, condensers,...

Words: 828 - Pages: 4

Free Essay

Heat Exchanger Design

...Design of heat exchangers required for a 50-100kW superheated Rankine cycle MECH 421 Huzeyfe SHAHIN Gokce SAGIR Usman Arshad SHAH 28th December 2015 Table of Contents 1. ABSTRACT .............................................................................................................................................. 3 2. INTRODUCTION ..................................................................................................................................... 3 3. LITERATURE REVIEW ............................................................................................................................. 3 4. SIMPLE DESIGN ..................................................................................................................................... 3 4.1 Evaporator at 800 kPa (Counter Flow) ................................................................................................ 4 4.1.1 Preheater ..................................................................................................................................... 4 4.1.2 Boiler ............................................................................................................................................ 4 4.1.3 Superheater ................................................................................................................................. 5 4.2 Evaporator at 800 kPa (Shell & Tube) ............................................

Words: 6124 - Pages: 25

Free Essay

Shell and Tube Heat Exchanger

...Effectively Design Shell-and-Tube Heat Exchangers To make the most of exchanger design software, one needs to understand STHE classification, exchanger components, tube layout, baffling, pressure drop, and mean temperature difference. Rajiv Mukherjee, Engineers India Ltd. T hermal design of shell-and-tube heat exchangers (STHEs) is done by sophisticated computer software. However, a good understanding of the underlying principles of exchanger design is needed to use this software effectively. This article explains the basics of exchanger thermal design, covering such topics as: STHE components; classification of STHEs according to construction and according to service; data needed for thermal design; tubeside design; shellside design, including tube layout, baffling, and shellside pressure drop; and mean temperature difference. The basic equations for tubeside and shellside heat transfer and pressure drop are wellknown; here we focus on the application of these correlations for the optimum design of heat exchangers. A followup article on advanced topics in shell-and-tube heat exchanger design, such as allocation of shellside and tubeside fluids, use of multiple shells, overdesign, and fouling, is scheduled to appear in the next issue. • baffles; and • nozzles. Other components include tie-rods and spacers, pass partition plates, impingement plate, longitudinal baffle, sealing strips, supports, and foundation. The Standards of the Tubular Exchanger Manufacturers Association (TEMA)...

Words: 11381 - Pages: 46

Free Essay

Heat Exchanger Lab

...School of Mechanical and Design Engineering   Dublin Institute of Technology Bachelor of Engineering Technology in Mechanical Engineering   Laboratory 2 Plate Heat Exchanger Assignment Robert O’Donovan Student Number: C12756051 Due Date: 24/10/2014 Lecturer: Jim Ffrench Dublin Institute of technology Bolton Street, Dublin 1. I.  Abstract   Heat exchangers are a piece of process equipment used for heat transfer between two media. The media do not come into direct contact and there is no mixing. Heat is transported from the hot medium to the cold medium by way of a heat conducting partition. In this experiment, we analysed the working principle of parallel and counter flow. We observed different fluid temperatures, fluid flow rates and how this affected the heat exchangers performance. Calculations were needed to determine the variation of the two configurations. There are some possible percentage errors that need to be considered in the experiment, these include the tube changeover from parallel to counter flow, the fluid loss will have an effect on the readings. Also if the unit is not allowed enough time to stabilise when changing the flow rates, the readings will not be accurate. 1"Vh"(L/min) Parallell"flow Counter"flow Vs U"= U"= 3"Vc"(L/min) 2.9"W/m 2 K 3.5"W/m 2 K The percentage difference between the U values is 20.6 %.   II.    Table  of  Contents     1.   INTRODUCTION  ...............

Words: 2209 - Pages: 9

Free Essay

Eg2002 Heat Exchanger

...EG2002 Process Engineering Continuous Assessment Report Heat Exchange Laboratory By Thomas A. Lindie 51011245 School of Engineering University of Aberdeen Kings College 2011-12 Table of Contents Contents Table of Contents I List of Figures II List of Tables II Symbols and Abbreviations III 1. Introduction 1 1.1 Background 1 1.2 Aims and Objectives 1 1.3 Structure of the Report 2 2. Background Theory 3 3. Experimental Methodology 6 4. Results 8 4.1 Tables of Co-Current and Counter-Current flow taken from Result Table 8 4.1.1 Table of Co-Current Flow at Steady State 8 4.1.2 Table of Counter-Current Flow at Steady State 8 4.2 Log Mean Temperature Different (LMTD) Calculations 9 4.3 Calculating the Duty of the HEX and the Efficiency 10 4.4 Graphs of Results for Co-Current and Counter-Current Flow 12 5. Discussion and Analysis 13 5.1 Log Mean Temperature Different (LMTD) Calculation Analysis 13 5.2 Efficiency of the Heat Exchanger 14 5.3 Errors in Laboratory 14 6. Conclusions and Recommendations 15 Bibliography 16 List of Figures Figure 1: 3D View of Shell and Tube heat exchanger taken from http://www.secshellandtube.com/ 3 Figure 2: Shell and Tube heat exchanger flow pattern taken from http://www.cheresources.com/content/articles/heat-transfer/specifying-a-liquid-liquid-heat-exchanger 3 Figure 3: Screenshot taken from co-current experiment on Armfield Programme 7 Figure 4:Graph of Co-Current Flow 12 ...

Words: 3933 - Pages: 16

Free Essay

Mea Heat Exchanger Design

...lean/rich MEA heat exchanger E-114. This heat exchanger is a counter flow shell and tube heat exchanger and is designed to heat up the rich MEA stream flowing from the CO2 absorber to the stripper. The principle that is applied is heat exchange between cold stream and hot stream which in this case the heat energy is transferred from the lean MEA stream to the rich MEA stream. Apart from this, the chemical engineering design for this heat exchanger includes the determination of its dimensions and heat exchange coefficient as well as pressure drop. The mechanical design covers the design of pressure vessel, head, supports and piping. In addition, the operating design which includes the commissioning, start-up, shutdown and maintenance procedures, process control, and HAZOP study is considered. 2.0 Process Description Figure 2.1 Schematic of rich/lean MEA heat exchange process flow sheet The lean/rich MEA heat exchange process is presented in Figure 2.1. The MEA-2 stream containing rich CO2 is flowing from CO2 absorber and enters the heat exchanger to be heated up from 61°C to 80°C by MEA-7 before entering the stripper. The MEA-7 is then cooled down from 105°C to 84°C when pass through the heat exchanger and recycle back to the CO2 absorber. The cold stream in this case is MEA-2 and MEA-3 while the hot stream is MEA-7 and MEA-8. 3.0 Chemical Engineering Design 3.1 Design Methodology The rich/lean MEA heat exchanger is a counter flow shell and tube heat exchanger. The chemical...

Words: 3516 - Pages: 15

Premium Essay

Optimization of Heat Exchanger Network

...journal homepage: www.elsevier.com/locate/apthermeng Optimization of heat exchanger network Mofid Gorji-Bandpy, Hossein Yahyazadeh-Jelodar, Mohammadtaghi Khalili* Noshirvani University of Technology, P.O. Box 484, Babol, Iran a r t i c l e i n f o Article history: Received 6 September 2010 Accepted 26 October 2010 Available online 2 November 2010 Keywords: Heat exchanger network (HEN) Optimization Genetic algorithm Pinch Analysis Method Mathematical Optimization Method Sequential Quadratic Programming (SQP) a b s t r a c t In this paper, a new method is presented for optimization of heat exchanger networks making use of genetic algorithm and Sequential Quadratic Programming. The optimization problem is solved in the following two levels: 1- Structure of the optimized network is distinguished through genetic algorithm, and 2- The optimized thermal load of exchangers is determined through Sequential Quadratic Programming. Genetic algorithm uses these values for the determination of the fitness. For assuring the authenticity of the newly presented method, two standard heat exchanger networks are solved numerically. For representing the efficiency and applicability of this method for the industrial issues, an actual industrial optimization problem i.e. Aromatic Unit of Bandar Imam Petrochemistry in Iran is verified. The results indicate that the proposed multistage optimization algorithm of heat exchanger networks is better in all cases than those obtained using traditional...

Words: 4334 - Pages: 18

Free Essay

Spartan Heat Exchangers Inc.

...SPARTAN HEAT EXCHANGERS INC. On June 10, Rick Coyne, materials manager at Spartan Heat Exchangers Inc. (Spartan), in Springfield, Missouri, received a call from Max Brisco, vice president of manufacturing: “What can materials department do to facilitate Spartan’s new business strategy? I’ll need your plan in next week.” SPARTAN HEAT EXCHANGERS Spartan was a leading designer and manufacturer of specialized industrial heat transfer equipment. Its customers operated in a number of industries such as steel, aluminium smelting, hydroelectricity generation, pulp and paper, refining, and petrochemical. The company’s primary products included transformer coolers, motor and generator coolers, air-cooled heat exchangers, and transformer oil coolers. Spartan’s combination of fin-tube and time-proven heat exchanger designs had gained wide recognition bot in North America and internationally. Sales revenues were $25 million and Spartan operated in a 125,000-square-foot plant. Spartan was owned by Krimmer Industries, a large privately held corporation with more than 10,000 employees worldwide, head-quartered in Denver. Rick Coyne summarized the business strategy of Spartan during the past ten years: “We were willing to do anything for every customer with respect to their heat transfer requirements. We were willing to do trial and error on the shop floor and provide a customer with his or her own unique heat transfer products.” He added, “Our design and manufacturing people derived greatest...

Words: 1117 - Pages: 5

Premium Essay

Essay On Heat Exchanger

...CHAPTER – 1 Introduction:- Heat exchangers are very helpful in chemical process, engineering application and also in daily use applications, such as, dairy industry, chemical industry, environment engineering, power production, air conditioning and also in food industry. Shell & Tube heat exchanger is commonly used in energy industries and petrochemical industry. Plate Heat Exchanger is commonly used in a wide range of chemical process and so many industrial functions. So many effort have been made to increase the heat transfer of heat exchanger, reduce the heat transfer time and also increase the energy utilization. The mixture of fluid (base liquid) and Nanoparticles (nanometer sized) are called 'nanofluid'. Latest technology gives benefit...

Words: 1646 - Pages: 7

Premium Essay

Heat Exchanger Research Paper

...Various Parts of Shell and Tube Heat Exchangers Shell Shell is the container for the shell fluid and the tube bundle is placed inside the shell. Shell is the costliest part of the heat exchanger. Cost of shell and tube heat exchanger sensitively changes with change in the diameter of shell. The clearance between the tube bundle and inner shell wall depends on the type of exchanger. As per the TEMA standard, shell size ranges from 6 in (152 mm) to 60 in (1520 mm). Standard pipes are available up to 24 in size (600 mm NB). If shell size is fabricated by rolling a plate. Shell diameter depends on tube bundle diameter. For fixed tube sheet shell and tube heat exchanger, the gap between shell and tube bundle is minimum, ranging from 10 to 20...

Words: 1200 - Pages: 5

Premium Essay

Cfd Analysis Of Double Pipe Heat Exchanger

...CHAPTER 5 CFD ANALYSIS OF DOUBLE PIPE HEAT EXCHANGER AND SIMULATION This chapter deals with the computational fluid dynamics (CFD) analysis of the hydrodynamics and thermal behavior of the turbulent flow through a 2 pass Double pipe heat exchanger using ANSYS FLUENT 14.0 software. 5.1 Geometry and Modeling 5.1.1 Specifications of Geometry and Boundary conditions The analysis is performed on a double pipe heat exchanger with the inner diameter of inner pipe is 0.019 m & outer diameter of inner pipe is 0.025 m, similarly for annulus pipe, the inner diameter of outer pipe is 0.05 m & outer diameter of outer pipe is 0.056 m and the total length of heat exchanger is 2.36 m (2-pass). The mass flow rate of hot water, mh (kg/s), is constant over annulus...

Words: 1372 - Pages: 6

Free Essay

Heat Exchanger

......................................................................................... 6  Discussion and Conclusion ...........................................................................................................................  9  References .................................................................................................................................................. 10  Appendix A ................................................................................................................................................. 11      2    Executive Summary  In order to design a good system for heat recovery from exhaust air, optimization on  cost and performance is the most important. To maximize the performance and reduce the  heat cost and annual cost on the recovery system, heat exchangers are the main part for the  optimization. The use of the Newton‐Raphson method is the most effective way to find the  minimum cost of the recovery system. There are four constraint equations and six unknowns  for the given system. MATLAB is used as the main method to solve them. The total cost of the  system including initial cost, electrical heating cost, pump power cost, and the component’s  cost is $13251 for a year. The initial cost is $7240, which is half of the total...

Words: 2354 - Pages: 10

Premium Essay

Spartan Heat Exchangers

...1. Spartan Heat Exchanger currently manufactures specialized industrial heat exchangers. The new business strategies for Spartan are emphasized on reducing product variety and standardize the product line. There are various implications associated with this strategy; firstly, Spartan’s current product line is based on job shop manufacturing operation where individual parts are produced in several departments and finally assembled in assembly area. Secondly, Spartan has multiple vendors for raw material supply and the materials department is using approximately 350 vendors. Thirdly, in the existing strategy, Spartan is using unique skilled workers. Finally, poor inventory management which reflects Spartan manufacturing operations are facing material shortage and stock outs. In order to opt for new strategy, Spartan has to make many changes and this process will certainly require time and efforts. For example, Spartan has to shift the manufacturing from batch process to assembly process. This will eventually require process reengineering; the reengineering will modify the existing department structure of manufacturing process. On the other side, Spartan has to reduce the number of suppliers; selection of the suppliers would be tedious task. In the assembly line manufacturing, Spartan will need skilled employees and hence, spend on the training on existing employees. Finally, the Spartan will have to improve their inventory management in order to avoid stock out...

Words: 1579 - Pages: 7

Premium Essay

Pressurized Water Reactor Steam Generator Material Problems Solutions to Prevent Capacity Loss and Extend Lifetime

...the steam generator, with both consequences resulting in a loss of profit to the operating utility. Specific problems associated with steam generator materials that are discussed include denting, stress corrosion cracking (SCC), phosphate thinning, as well as vibration and mechanical problems. A connection is established between material issues that affect steam generators and capacity losses as well as decreased lifetime. Finally, solutions are discussed to prevent decreases in capacity and diminished lifetime. Introduction Steam generators are a critical component of PWR. The function of a steam generator in a PWR is to serve as a heat exchanger between the primary and secondary. The heat exchange that occurs between the primary and secondary creates steam, the steam turns a turbine, the process of which generates electricity. The generation of electricity for profit is the purpose of nuclear power plants, therefore material problems associated with steam generators that reduce the capacity of a nuclear power plant to generate electricity are an important profit consideration. Another significant cost and profit consideration is steam generator replacement cost and replacement power costs during the outage. The solving of steam generator tube-related material problems and the maximization of...

Words: 1771 - Pages: 8